1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Remote I/O
From: Wesley Moore <[email protected]>
To: Paul Hamadyk <[email protected]>
Cc: EPICS Tech Talk <[email protected]>
Date: Fri, 18 Dec 2009 11:11:46 -0500
Paul Hamadyk wrote:
On Thu, 2009-12-17 at 09:07 -0500, Wesley Moore wrote:

I'm using the CJ1's as well paired with the ETN21 Ethernet module. I believe one I'm using has the built in Ethernet but it's basically the same. The Ethernet driver uses the FINS protocol. I can read/write bits or words to the PLC. The memory areas I read/write to are DM, CIO, WR, and HR. I've found pretty quick that reading by word and splitting out the bits to individual bi and bo's was the way to go. Much faster that way. I've got the driver working in EPICS 3.13 and 3.14.


Wesley

I will be making a streams protocol file for FINS/UDP, using asyn's
UDP/IP for the request and UDP/IP Server for the reply, if you're
interested? Can you think of any advantages in using your Ethernet
driver?

We tend to use Data Memory (DM) with a bit of Core IO (CIO) and
Auxiliary Registers (AR) for PLC status and error information.

Paul.
Paul,
I'd be interested in using that at a later date. The biggest part of why I went the driver route was that I started with one from KEK. The driver didn't work out of the box, parts of the FINS protocol were hard coded and some data types didn't work. One thing to be mindful of is the Gateway Counter. It's set to 2 or 7 I believe. Either way, the EPICS side just has to match. As far as memory areas, I use the HR area for interlocks that need to hold through a power cycle.
Wesley
begin:vcard
fn:Wesley Moore
n:Moore;Wesley
org:Thomas Jefferson National Accelerator Facility;Free Electron Laser
adr:Suite 19, MS 18;;12000 Jefferson Avenue;Newport News;VA;23606;USA
email;internet:[email protected]
title:FEL Computer Scientist
tel;work:(757) 269-6033
tel;fax:(757) 269-6384
tel;pager:(757) 584-6033
url:http://www.jlab.org/FEL/
version:2.1
end:vcard


References:
Remote I/O nick.rees
Re: Remote I/O Matthias Clausen
Re: Remote I/O Ralph Lange
Re: Remote I/O Matthias Clausen
RE: Remote I/O Dalesio, Leo
Re: Remote I/O Matthias Clausen
Re: Remote I/O Wesley Moore
Re: Remote I/O Paul Hamadyk
Re: Remote I/O Wesley Moore
Re: Remote I/O Paul Hamadyk

Navigate by Date:
Prev: Re: Remote I/O David Dudley
Next: Re: mbboDirect problem Andrew Johnson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Remote I/O Paul Hamadyk
Next: Re: Remote I/O David Dudley
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 31 Jan 2014 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·