EPICS Controls Argonne National Laboratory

Experimental Physics and
Industrial Control System

1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Remote I/O
From: Matthias Clausen <[email protected]>
To: Ralph Lange <[email protected]>
Cc: EPICS Tech Talk <[email protected]>
Date: Wed, 16 Dec 2009 16:02:36 +0100
Hi Ralph,

Ralph Lange wrote:
On Wed 16 Dec 2009 8:16:17 Matthias Clausen wrote:
Hi Nick,

[...] In our case sensors and actors are directly connected to Profibus. The remaining I/O is connected through WaGo I/O with a Profibus controller. Profibus driver and configuration is available from us - even with redundancy support...

Hi Matthias,

is that using the 1996 IPAC-Profibus Interface that is listed in the hardware support database on the EPICS web site?
no - it's a new driver which support the Softing PC 104 cards. Softing is now producing also a Compact PCI card for us. There's a special firmware available which supports redundant Profibus connections and fail-over - in conjunction with the redundant IOC.

Configuring Profibus (DP - or PA) is quite complicated. You have to map memory space of the I/O devices into the DPM on the IOC. So you need to configure your records's addresses in a way that they match with the DMP layout. We have developed a configuration tool in CSS which creates an XML file. (Like the Siemens 'Step 7' tool) This file is parsed on the IOC and creates the memory layout in the DPM. The EPICS records get their Profibus address from a reference in the configuration database. (When the db files gets created)

We should finally write some documentation about it ;-))

Thanks
-Matthias

Ralph



--
------------------------------------------------------------------------
Matthias Clausen                         Cryogenic Controls Group(MKS-2)
phone:  +49-40-8998-3256                Deutsches Elektronen Synchrotron
fax:    +49-40-8994-3256                                    Notkestr. 85
e-mail: [email protected]                           22607 Hamburg
WWW-MKS2.desy.de                                                 Germany
------------------------------------------------------------------------


Replies:
RE: Remote I/O Dalesio, Leo
References:
Remote I/O nick.rees
Re: Remote I/O Matthias Clausen
Re: Remote I/O Ralph Lange

Navigate by Date:
Prev: RE: Remote I/O nick.rees
Next: Re: Remote I/O David Dudley
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: Remote I/O nick.rees
Next: RE: Remote I/O Dalesio, Leo
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 31 Jan 2014 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·