1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: Modbus help
From: "Mark Rivers" <[email protected]>
To: <[email protected]>, <[email protected]>
Date: Tue, 24 Nov 2009 11:32:01 -0600
Hi Emma,

Here are some questions/suggestions:

- Can you send your startup script?  
- How have you set the interpose interface, etc?  
- Does your device use serial/RTU (binary) or serial/ASCII protocol?  
- What is the slave address of your device?
- You have turned on asynTrace for the underlying asyn serial port.
Please also turn on asynTrace for the Modbus asyn port.  That should be
very helpful.

Once I know how it is configured I can figure out if those 8 characters
it is sending are correct.

Mark


-----Original Message-----
From: [email protected]
[mailto:[email protected]] On Behalf Of
[email protected]
Sent: Tuesday, November 24, 2009 10:52 AM
To: [email protected]
Subject: Modbus help

Hi,

I'm trying to get an RS-485 chain of N2300 temperature monitors talking
to EPICS using the asyn modbus support (R1-3) and so far am not having
much luck.  Basically I just get no response back from any of them,
although I'm pretty confident I'm sending out the right message (I
checked it with a serial analyser) and have configured the correct comms
setting.

After iocInit I get the following message on the console (with asynTrace
turned on):

2009/11/24 16:03:34.302 drvModbusAsyn::doModbusIO port readTemp is
disconnected

and then lots of I/O errors:

02 03 00 01 00 01 d5 f9
2009/11/24 16:03:38.952 drvModbusAsyn::doModbusIO port readTemp error
calling writeRead, error=, nwrite=5/5, nread=0
2009/11/24 16:03:39.302 ME02P-DI-TMON-01:TEMP1 devAsynFloat64::process
read error
2009/11/24 16:03:40.452 drvModbusAsyn::doModbusIO port readTemp has I/O
error
2009/11/24 16:03:40.452 /ty/72/0 write 8

02 03 00 01 00 01 d5 f9
2009/11/24 16:03:41.952 drvModbusAsyn::doModbusIO port readTemp error
calling writeRead, error=, nwrite=5/5, nread=0
2009/11/24 16:03:43.452 drvModbusAsyn::doModbusIO port readTemp has I/O
error
2009/11/24 16:03:43.452 /ty/72/0 write 8

....... etc

asynReport prints the following:

modbus port: readTemp
    asynOctet server:   ty_72_0
    modbusFunction:     3
    modbusStartAddress: 01
    modbusLength:       01
    plcType:            N2300
    I/O errors:         119
    Read OK:            0
    Write OK:           0
    pollDelay:          1.500000
    Time for last I/O   0 msec
    Max. I/O time:      0 msec
value = 0 = 0x0

Am I likely to be chasing a wiring/hardware issue here or is there
something standing out that indicates a problem higher up? This is the
first time I've tried to use modbus so I'm not sure what a 'working'
system looks like!

Thanks in advance,

Emma


-- 
This e-mail and any attachments may contain confidential, copyright and
or privileged material, and are for the use of the intended addressee
only. If you are not the intended addressee or an authorised recipient
of the addressee please notify us of receipt by returning the e-mail and
do not use, copy, retain, distribute or disclose the information in or
attached to the e-mail.
Any opinions expressed within this e-mail are those of the individual
and not necessarily of Diamond Light Source Ltd. 
Diamond Light Source Ltd. cannot guarantee that this e-mail or any
attachments are free from viruses and we cannot accept liability for any
damage which you may sustain as a result of software viruses which may
be transmitted in or with the message.
Diamond Light Source Limited (company no. 4375679). Registered in
England and Wales with its registered office at Diamond House, Harwell
Science and Innovation Campus, Didcot, Oxfordshire, OX11 0DE, United
Kingdom
 






Replies:
RE: Modbus help emma.shepherd
References:
Modbus help emma.shepherd

Navigate by Date:
Prev: RE: CA problem w EPICS 3.14.11 & VxWorks 6.7 Jeff Hill
Next: (Another) Modbus problem Stephen Lewis
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Modbus help emma.shepherd
Next: RE: Modbus help emma.shepherd
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 31 Jan 2014 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·