On Friday 13 November 2009 13:38:36 Geoff Savage wrote:
I have a passive stringout record in IOC A whose OUTLINK references an
mbbo record in IOC B. When I reboot IOC B the value in the stringout
record is written to the mbbo record even though the stringout record
has not been processed.
A bit more background. The stringout record will be processed by a
calc record when a temperature becomes too high. The mbbo record
controls the power to a front end board. So the value being written
is to power off the front end board whenever the IOC B is rebooted.
This doesn't sound like it should be happening, unless there's something else
going on. Have you tried setting TPRO on the mbbo record? The output from
dblsr "<mbboRecordName>", 2
might provide some more clues as well.
Can you post the two complete record definitions extracted from their .db
files, and the output from dbpr on both records with an interest level 3 or
higher. Also the Base version number that you're running (and whether it
contains any significant modifications to the official release), and the
target architectures of the two IOCs for completeness sake.
- Andrew