-----Ursprüngliche Nachricht-----
Von: Szalata, Zenon M. <[email protected]>
Gesendet: 17.9.'09, 21:23
Is it possible to setup a "longin" record to generate a monitor each time it is processed regardless whether the VAL value changes or not? If so, how do I do it?
Just set MDEL to -1
That'll do the job...