1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Asyn changes
From: Eric Norum <[email protected]>
To: Tech-talk Techtalk <[email protected]>
Date: Fri, 3 Apr 2009 05:48:03 -0500
Several changes have been made to the ASYN support module at this week's EPICS codeathon. Here's your chance to comment on them before they become part of the next release.

1. asynReport at detail level 0 now reports only disconnected subaddresses. The previous level 0 report was far too long for register-based devices that sometimes had scores (or even hundreds) of addresses in completely benign states.

2. The autoconnect code has undergone considerable modification. When a port is registered with autoConnect true, or whenever a port disconnect exception is raised on an autoConnect port, an attempt at connection occurs immediately followed by retry attempts at 20 second intervals. Attempts to queue requests to a disconnected port (even an autoConnect port) will be rejected. These changes have been made to reduce the occurences of 'connection flurries' and to ensure that requests do not languish in the queue when connections are broken.

3. Setting the trace mask or trace I/O mask for a port now also sets the trace mask or trace I/O mask for every device associated with that port.

4. Passing a NULL pasynUser argument to the setTraceMask and setTraceIOMask will set the asynBase (default) trace mask or trace I/O mask. Previously there was no mechanism for changing the default trace masks.

5. Add new asynStatus codes, asynDisconnected and asynDisabled. Attempts to queue a request to a disconnected or disabled port return these codes, respectively. Future changes to record support may propogate these to the record alarm status field.

--
Eric Norum <[email protected]>
Advanced Photon Source
Argonne National Laboratory
(630) 252-4793



Navigate by Date:
Prev: ai record with dtyp of "raw soft channel" Patrick Thomas
Next: Re: Asyn changes Eric Norum
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: ai record with dtyp of "raw soft channel" Ralph Lange
Next: Re: Asyn changes Eric Norum
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 31 Jan 2014 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·