1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: connections with pasynOctetSyncIO->connect
From: "Mark Rivers" <[email protected]>
To: "John Hammonds" <[email protected]>, "Tech Tech Talk" <[email protected]>
Date: Tue, 31 Mar 2009 06:55:05 -0500
John,
 
I think that if it returns asynSuccess you should ignore the error message, because it may be stale.
 
What do you see if you turn on asynTrace and do some writes?  Does the driver claim to be writing?  What type of communication port is this?
 
Mark
 

________________________________

From: [email protected] on behalf of John Hammonds
Sent: Mon 3/30/2009 11:21 PM
To: Tech Tech Talk
Subject: connections with pasynOctetSyncIO->connect



What checks should be done to verify a connection with
pasynOctetSyncIO->connect?  I have a driver that calls this.  The return
value is asynSuccess but the pasynUser->errorMessage is "port usaxsEns
or addr -1 not connected" and we see no communication.

Thanks,
John

--
John Hammonds
Beamline Controls and Data Acquisition Group
APS Engineering Support Division

Argonne National Laboratory
[email protected] <mailto:[email protected]>
(630)252-5317







Replies:
Re: connections with pasynOctetSyncIO->connect John Hammonds
References:
connections with pasynOctetSyncIO->connect John Hammonds

Navigate by Date:
Prev: Re: Smoothing and alarm filtering on the analog input record - a proposal Dirk Zimoch
Next: Bug in dbGetNElements Benjamin Franksen
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: connections with pasynOctetSyncIO->connect John Hammonds
Next: Re: connections with pasynOctetSyncIO->connect John Hammonds
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 31 Jan 2014 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·