1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: EPICS asyn error message
From: "Mark Rivers" <[email protected]>
To: "Richard Pastrick" <[email protected]>, <[email protected]>
Date: Mon, 12 Jan 2009 21:07:32 -0600
Richard,
 
The drvAsynIPPortConfigure command is used to create a new asyn port, which you have called "pmac0".  drvAsynMotorConfigure also creates a new asyn port, which you have also called "pmac0".  That is not legal, you must use a different name.  Use another name, like pmacMotor0 for the drvAsynMotorConfigure command.  That is the port name you will use in your subsitutions file for motor records.
 
Mark
 

________________________________

From: [email protected] on behalf of Richard Pastrick
Sent: Mon 1/12/2009 7:48 PM
To: [email protected]
Subject: EPICS asyn error message



I am running into some problems while trying to setup a Delta Tau UMAC to communicate over IP with an EPICS server. I am simply trying to get the asyn interface to work at this point.

 

I receive the following error messages when I run the following commands:

 

drvAsynIPPortConfigure("pmac0","172.24.68.50:1025",0,1,0)

drvAsynMotorConfigure("pmac0", "pmacAsynMotor", 0, 6)

 

asynCommon:registerDriver pmac0 already registered

dryAsynMotorConfigure Error: Can't register port

 

I am using base 3.14.8.2, asyn 4.9, and motor r6-3. The implementation I am trying to use is the synApps tpmac available from http://www.gmca.aps.anl.gov/TPMAC2/

 

I have looked at all of the example .src files that I could find in epics downloads but to no avail and I am very confused right now. Any help that any of you can give would be greatly appreciated.

 

Thank you.

 

Richard Pastrick

Associate Software Engineer

Xradia Inc

5052 Commercial Cir

Concord CA 94520

925-288-1228 Ext 1151

925-348-0384 (cell)

 


________________________________

The information in this email, including any attachments, is confidential and intended only for the recipient(s) listed. Any use of this email for any other purpose is prohibited. If you have received this email in error, please notify me immediately by reply email, delete this email, and do not disclose its contents to anyone.



References:
EPICS asyn error message Richard Pastrick

Navigate by Date:
Prev: 答复: MAXvSetup is an undefined symbol 汪启胜
Next: RE: EPICS asyn error message Rees, NP (Nick)
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: EPICS asyn error message Richard Pastrick
Next: RE: EPICS asyn error message Rees, NP (Nick)
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  <20092010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 31 Jan 2014 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·