1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: -- OMS58 PROBLEM Sevr = minor Motor motion timeout ERROR on card 0, signal 2 --
From: Ron Sluiter <[email protected]>
To: [email protected]
Cc: [email protected]
Date: Thu, 19 Jun 2008 09:28:55 -0500
Hello Jerome,

The message means that the OMS VME58 driver has not detected any
change in the position feedback after 10 polling samples while the motor
was supposed to be moving.

You either have a problem with your position feedback device or the
motor is being moved very slowly with a high polling rate (i.e. the last
argument in "oms58Setup").

Hope this helps,
Ron

[email protected] wrote:
Hello all,

I have some troubles with command HOMR on driver OMS58-4S with servo amplifier
and with a resolver feedback go to oms board.
i have a error message wich indicate a strange timeout whiche come from epics driver v6.22
A message is :
"Sevr = minor Motor motion timeout ERROR on card 0, signal 2"


thanks you per advance

JEROME HOSSELET




References:
-- OMS58 PROBLEM Sevr = minor Motor motion timeout ERROR on card 0, signal 2 -- Jerome . Hosselet

Navigate by Date:
Prev: -- OMS58 PROBLEM Sevr = minor Motor motion timeout ERROR on card 0, signal 2 -- Jerome . Hosselet
Next: edm 1-11-1g segfault in FC9 Kevin Anderson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: -- OMS58 PROBLEM Sevr = minor Motor motion timeout ERROR on card 0, signal 2 -- Jerome . Hosselet
Next: edm 1-11-1g segfault in FC9 Kevin Anderson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 02 Sep 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·