1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: Listen to multiple events
From: "Allison, Stephanie" <[email protected]>
To: "Emmanuel Mayssat" <[email protected]>, "Korhonen Timo" <[email protected]>
Cc: Dehong Zhang <[email protected]>, [email protected]
Date: Tue, 18 Mar 2008 11:47:40 -0700
Hi Emmanuel,

> > > record(event, "Test:Event1") {
> > >   field(DTYP, "MRF Event Receiver")
> > >   field(INP, "#C0 S1 @")
> > >   field(SCAN, "I/O Intr")
> > >   field(VAL, "1")
> > >   field(FLNK, "Test:RecordToProcessOnEvent1or2")
> > > }
> 
> When I red the above, I was a little confused.
> event records are usually generating events, not receiving them.(source
> epics record manual). The record above seems to be using a DTYP I am
> unfamiliar with. Where can I find the source? Is that event driver
> specific?

It is event-driver specific and this is for the Micro-Research Finland EVR 200 or 230.  I neglected to add the event control record (erevent) that is needed for this record to ever process.  There is a nice discussion of this mechanism in section 5.1.2 of the "Global Event System" documentation (version 3):
 http://www.slac.stanford.edu/grp/lcls/controls/global/subsystems/timing/globalEventV3.htm
(sorry, I can't find the APS link to this document).

Eric Bjorkland has the source but it's only useful for MRF EVRs.

Stephanie


References:
Listen to multiple events Dehong Zhang
RE: Listen to multiple events Allison, Stephanie
Re: Listen to multiple events Korhonen Timo
Re: Listen to multiple events Emmanuel Mayssat

Navigate by Date:
Prev: Re: Listen to multiple events Emmanuel Mayssat
Next: Severity of I/O interrupt records Schuh, Stephen
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Listen to multiple events Emmanuel Mayssat
Next: Re: Listen to multiple events Korhonen Timo
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 02 Sep 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·