1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Problem with aborting motor record
From: "Rarback, Harvey" <[email protected]>
To: <[email protected]>
Date: Mon, 17 Mar 2008 13:19:02 -0700
	Motor record gurus,

This is another one of those difficult-to-reproduce problems I am having with the motor record.

I am using motor driver version 6.22 (with SLAC modifications for RTEMS) on EPICS base 3.14.8.2.  The hardware is an OMS MAXv-8000 motor controller along with Kramert 505F SSI encoder readout.  I have configured the motor record to have backlash correction and multiple retries.  Occasionally when I try to abort a move (sending a 1 to the STOP field), usually near the time of backlash correction or small retry move, the DMOV field does not get set to 1 after the abort.  What I do see is that the ST command gets sent to the motor hardware, the hardware returns status "PDNN", the done bit in the Motor Status (MSTA) field get set and the MOVN field is set to 0.  If the motor status returns "PNNN" it seems to set the DMOV field ok.  The only way I am able to move the motor again is to reboot the IOC to set the DMOV field.

Does anyone know what is happening here?  Is there a less destructive way to recover from this situation (MOVN and DMOV both 0)?

Thanks.

                                 --Harvey Rarback



Replies:
Re: Problem with aborting motor record Ron Sluiter
References:
FW: Problem with soft motor record Rarback, Harvey

Navigate by Date:
Prev: RE: Problem with soft motor record Rarback, Harvey
Next: Re: Problem with aborting motor record Ron Sluiter
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: Problem with soft motor record Rarback, Harvey
Next: Re: Problem with aborting motor record Ron Sluiter
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  <20082009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 02 Sep 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·