On 11/1/07, Emmanuel Mayssat <[email protected]> wrote:
There is a standard record called "compress" that may be another alternative. A compress record can work as a circular waveform or
circular buffer or FIFO stack. I use it with my ADC to have scrolling waveform. If I increase the SCAN rate, I don't get as many samples as with a bigger one, but I get a very smooth scrolling ;-)
Yes, but I'm pretty sure I should get the entire waveform, we need some calculation on that. And thank you all the same.
In other words, with the compress you don't need to fetch the entire waveform at once. Not sure it will help in your case, but just wanted to
remind everybody about the compress record.
> waveforms I registered. So it will take 40*timescale to get all I want > because I've told that my product---DPO7054---used only one probe for > all four channels. Before I get the waveform, the buffer is locked and
> will never refresh in my case.
You probably have 2 pointers on your on-device memory (a circular buffer most likely). One points to the last sample you read, the other to the last updated samples. The newly acquired samples are those between those
2 pointers.
> > I know I can set SCAN to a very big number but, when the time scale is > small, I think it's not efficient then. I'm just wondering whether I > could use another record to control it, or something alternative.
Below is probably what you want to put in your db file. Beware that my menuScan.dbd is not the default one, so you probably will have to change the SacanRateMO labels.
record(event, "$(deviceName):ScanOnceEV") {
field(DESC, "Scan once event") field(VAL, "$(scanOnceEventNumber)") field(SCAN, "Passive") }
record(mbbo, "$(deviceName):ScanRateMO") {
field(DESC, "Selectable scan rate") field(VAL, "$(scanRate)") field(ZRST, "Passive") field(ZRVL, "0") field(ONST, "Event $(scanOnceEventNumber)")
field(ONVL, "1") field(TWST, "I/O Intr") field(TWVL, "2") field(THST, ".1 second") field(THVL, "3") field(FRST, ".2 second")
field(FRVL, "4") field(FVST, ".5 second") field(FVVL, "5") field(SXST, "1 second") field(SXVL, "6") field(SVST, "2 second")
field(SVVL, "7") field(EIST, "5 second") field(EIVL, "8") field(NIST, "10 second") field(NIVL, "9") field(TEST, "20 second")
field(TEVL, "10") field(ELST, "50 second") field(ELVL, "11") field(TVST, "1 minute") field(TVVL, "12") field(TTST, "2 minute")
field(TTVL, "13") field(FTST, "5 minute") field(FTVL, "14") field(FFST, "10 minute") field(FFVL, "15") field(OUT, "$(deviceName):
ScanEnblFO.SCAN") field(PINI, "YES") field(FLNK, "$(deviceName):ScanRateSI") } record(stringin, "$(deviceName):ScanRateSI") { field(SCAN, "Passive")
field(DESC, "Scan rate readback") field(INP, "$(deviceName):ScanEnblFO.SCAN") field(DTYP, "Soft Channel") }
That's a little too complicated for me. I'll figure that out later.
> > > Thanks for any input. > > -- > Best Regards > Chen > ----------------------------------------------------------------
> > Zhi-chu Chen | Shanghai Synchrotron Radiation Facility > No. 2019 | Jialuo Rd. | Jiading | Shanghai | P.R. China > tel: 086 21 5955 3405 |
zhichu.chen.googlepages.com > | www.sinap.ac.cn > ----------------------------------------------------------------
-- Best Regards Chen ----------------------------------------------------------------
Zhi-chu Chen | Shanghai Synchrotron Radiation Facility No. 2019 | Jialuo Rd. | Jiading | Shanghai |
P.R. China tel: 086 21 5955 3405 | zhichu.chen.googlepages.com | www.sinap.ac.cn
----------------------------------------------------------------
- References:
- Is there any chance that I can change SCAN parameter dynamically? Zhichu Chen
- Re: Is there any chance that I can change SCAN parameter dynamically? Emmanuel Mayssat
- Navigate by Date:
- Prev:
Documentation on pv crawler, etc. Eric Berryman
- Next:
Re: GpibBoardDriverConfig not found zhangdemin99
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
<2007>
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: Is there any chance that I can change SCAN parameter dynamically? Emmanuel Mayssat
- Next:
Documentation on pv crawler, etc. Eric Berryman
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
<2007>
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|