1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  <20072008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  <20072008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: Question about CA and optimization
From: "Jeff Hill" <[email protected]>
To: "'Heinrich du Toit'" <[email protected]>, "'TechTalk EPICS'" <[email protected]>
Date: Thu, 27 Sep 2007 09:18:44 -0600
> If I run CA inside an IOC and connect to a PV inside the same IOC.
> Does this in effect really bypass the CA networking part and uses
> direct DB access to that PV since it's inside the same program?

If an applications using the CA client library is running inside of an IOC
and its channel is connected to a PV in that same IOC no TCP/IP circuit is
created, and the client application's requests are directly translated into
db_access.h calls.

Jeff

> -----Original Message-----
> From: [email protected] [mailto:tech-talk-
> [email protected]] On Behalf Of Heinrich du Toit
> Sent: Thursday, September 27, 2007 4:14 AM
> To: TechTalk EPICS
> Subject: Question about CA and optimization
> 
> 
> I just want to clarify something.
> 
> If I run CA inside an IOC and connect to a PV inside the same IOC.
> Does this in effect really bypass the CA networking part and uses
> direct
> DB access to that PV since it's inside the same program?
> 
> Or do you need to do something special to enable this optimization
> thingy :)
> 
> thanx
> -Heinrich


References:
Question about CA and optimization Heinrich du Toit

Navigate by Date:
Prev: Re: Question about CA and optimization Heinrich du Toit
Next: RE: same PV on multiple IOC's - side effect Jeff Hill
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  <20072008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Question about CA and optimization Heinrich du Toit
Next: CA inside IOC - shutdown problem Heinrich du Toit
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  <20072008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Nov 2011 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·