1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  <20072008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  <20072008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: AutoSave - errors?
From: Tim Mooney <[email protected]>
To: Heinrich du Toit <[email protected]>
Cc: TechTalk EPICS <[email protected]>
Date: Wed, 26 Sep 2007 08:17:04 -0500


Heinrich du Toit wrote:
In auto save documentation it says "Autosave is not completely
bulletproof" and that at APS you have problems at times.

Can you maybe explain to me what the effect of these problems are?
Does the IOC stop working? does it load "corrupted" data or something.
Or does it simply not completely restore?

Thanx
-Heinrich


Not restore.


Most of the data I have is for the version of autosave in synApps 4.6.
For that version, problems include failure to save parameter values
because the save task crashed, the task had a stale file handle, one
save operation took long enough to overlap with the next save operation,
or unknown causes.  I don't have any record of a released version of
autosave restoring corrupted data, or causing some other problem in an
ioc.  It's all about failure to restore parameter values, and this is
nearly always caused by an earlier failure to save them.

For recent versions of autosave, I have so far two instances of failure
to save parameter values, and complaints about unwarranted error messages.
There is more version-specific information on the autosave web page, and
in release notes:

www.aps.anl.gov/aod/bcda/synApps/autosave/autosave.html


-- Tim Mooney ([email protected]) (630)252-5417 Beamline Controls & Data Acquisition Group Advanced Photon Source, Argonne National Lab.

References:
AutoSave - errors? Heinrich du Toit

Navigate by Date:
Prev: channelWatcher Heinrich du Toit
Next: same PV on multiple IOC's - side effect Heinrich du Toit
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  <20072008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: AutoSave - errors? Heinrich du Toit
Next: error linking with cmlog Heinrich du Toit
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  <20072008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Nov 2011 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·