Folks,
I have released a new version of the Modbus module.
- Fixed a bug in computing byteCount in the WRITE_MULTIPLE_COILS
function code. This was preventing that function code from working
correctly on some PLCs.
- There is a known limitation with using serial interfaces. It is not
currently possible to have multiple Modbus servers connected to a single
serial port. This is a limitation of the asynInterposeInterface
architecture used. It may be fixed in a future release.