On Wednesday 13 June 2007 03:13, Luedeke Andreas wrote:
> Of course you can use PP on input links, too:
> it causes the record that the link points to to process before the data
> is read from the link.
Caveat: the data you get over a PP input link might be stale (i.e. not the
new value but the old one from the last processing) if the record that the
link points to is processed asynchronously. Whether processing is
synchronous or asynchronous is mostly decided by the device support.
Cheers
Ben