> From: Mark Rivers [mailto:[email protected]]
> - Do you know of any other sites that might have already done
> a 3.14 OSI conversion? How are new accelerators (Diamond,
> Australian, Canadian) communicating to PLCs from EPICS? Are
> they using MODBUS or some other protocol?
Diamond is using Omron PLCs, communicating via the HostLink protocol
over RS232 serial lines.
We have a StreamDevice protocol file to do the protocol handling, and an
Asyn serial driver. In order to reduce overhead on the communication
path, though, some applications transfer large blocks of data from the
PLC memory, and then use a series of subarray records to extract the
required data from the correct position.
--
Peter Denison, Senior Software Engineer
Diamond Light Source Ltd., Diamond House, Chilton, Didcot, Oxon, OX11
0DE
Tel: +44 1235 778511
- References:
- RE: MODBUS communication with H2-ECOM100 AuotmationDirect DL205 system? Mark Rivers
- Navigate by Date:
- Prev:
Re: MODBUS communication with H2-ECOM100 AuotmationDirect DL205 system? Rolf Keitel
- Next:
RE: MODBUS communication with H2-ECOM100 AuotmationDirect DL205 system? Elder Matias
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
<2007>
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: MODBUS communication with H2-ECOM100 AuotmationDirect DL205 system? Rolf Keitel
- Next:
RE: MODBUS communication with H2-ECOM100 AuotmationDirect DL205 system? Elder Matias
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
<2007>
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|