1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: Scaling Database entries
From: "David Dudley" <[email protected]>
To: <[email protected]>
Date: Tue, 14 Nov 2006 08:37:27 -0600
Two point scaling I understand.  What I haven't figured yet is where I put it in.

Where(how) do I set the deviceHigh and deviceLow variables, or is that expected in the device driver?  And if it is in the device driver, does that mean that I'm going to have to have a separate device entry for each device that has a different dynamic range?

Dynamic range calculations are not handled inside EPICS?

I've got a number of different dynamic ranges for the different devices here, do they all have to be separately scaled inside the device driver to a standard range, or can EPICS be set to adjust for the dynamic ranges?

Most of the software (make that *all*) I've used previously had the ability to have the RAWLOW and RAWHIGH values set, and they they did the scaling themselves.  Seems an omission if EPICS can't do that?

David

>>> "Mark Rivers" <[email protected]> 11/13/06 8:22 PM >>>
Device support must have a "convert" routine that does a calculation like the following to compute .ESLO and .EOFF
 
        precord->eslo = (eguf - egul)/(deviceHigh - deviceLow);
        precord->eoff = (deviceHigh*egul - deviceLow*eguf)/
                        (deviceHigh - deviceLow);
 
Mark

 
________________________________

From: David Dudley [mailto:[email protected]] 
Sent: Mon 11/13/2006 8:07 PM
To: [email protected] 
Subject: Scaling Database entries



OK guys,

My modbus driver is starting to work, and now I'm linking up with some of the PLC's in the plant.  Now, I've started working on building the database for the first site.

Here's my question:

I've got some AI signals that come from one of the PLCs.  Raw values on some are scaled 0-32000, while others are scaled 800-32000, and others have raw values from -32768-32767.  I see the definitions for the EGUL and EGUF values, but how do I set the RAW input ranges?  Also, I've got some flow meter values that have to be scaled from linear to square root values..

David Dudley
City of Corpus Christi






BEGIN:VCARD
VERSION:2.1
X-GWTYPE:USER
FN:David Dudley
TEL;WORK:880-3740
ORG:;MIS
TEL;PREF;FAX:880-3741
EMAIL;WORK;PREF;NGW:[email protected]
N:Dudley;David
END:VCARD


Replies:
Re: Scaling Database entries Kay-Uwe Kasemir
Re: Scaling Database entries Dirk Zimoch

Navigate by Date:
Prev: RE: devSNMP: Thread error? Kagarmanov, Albert
Next: devSNMP: Thread error? Bertrand H.J. Biritz
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: Scaling Database entries Mark Rivers
Next: Re: Scaling Database entries Kay-Uwe Kasemir
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 02 Sep 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·