Experimental Physics and Industrial Control System
Thank you Tim, I overlooked the basics ;-)
The record type associated with the PV in the db file was analog input
(ai). Also in the dbd with the device definition, the analog input
record was wrongly associated with the new dset. As a result, epics or C
did not give any indicating error at compilation time.
For your information.
--
Emmanuel
On Sun, 2006-07-23 at 12:06 -0500, Tim Mooney wrote:
>
> Probably something didn't get changed from it ai-recordtype value to its
> new-recordtype value. For example, does the .dbd file still say
> recordtype(ai) {
>
> If you send copies of the .dbd and .c files, I'll look for a problem.
>
- References:
- Record fields not accessible in iocsh / database Emmanuel Mayssat
- Navigate by Date:
- Prev:
Re: Off -Line Storage of Archiver Data - Request for Information Ernest L. Williams Jr.
- Next:
Measurment Computing PC104-GPIB John Lee