Subject: Re: Digitizer needed for LCLS
From: Peter Milne <Peter.Milne@d-tacq.com>
To: Steve Lewis <SALewis@llnl.gov>
Cc: tech-talk@aps.anl.gov, Elden Ables <ables1@llnl.gov>
Date: Tue, 02 May 2006 10:21:15 +0100
Hi Steve

Do take a look at D-TACQ ACQ196CPCI : 96 simultaneous differential channels, 16 bit resolution, one slot.
http://www.d-tacq.com/acq196cpci.shtml


The card runs Linux, has Ethernet connectivity and runs an EPICS IOC on board.
So a single card in its own private 1U chassis could meet your requirement.


Regarding your specific application, we have a burst streaming mode that will support rapid short bursts;
The EPICS IOC doesn't support this mode at the moment, but it isn't a million miles away either.


Best regards


Peter.



Steve Lewis wrote:


EPICS colleagues:

The LLNL group that is supplying the diagnostics to commission the LCLS needs a digitizer for an energy measurement instrument (calorimeter) with the following characteristics:

- 100 channels sampled simultaneously
- each channel takes 100 samples at 10us per sample (1 ms total time)
- differential inputs
- 12 bits minimum; 14 or even 16 bits preferred
- sampling repeats at 120 Hz major cycle with trigger

A VME or VXI format is ideal.

Any suggestions are most welcome. Ideally, we can discuss this in depth at the June meeting.



--
Peter Milne			Peter.Milne@d-tacq.com
D-TACQ Solutions Ltd		www.d-tacq.com


References:
Digitizer needed for LCLS Steve Lewis

Navigate by Date:
Prev: Re: Who can help with dbLoadRecords()? Benjamin Franksen
Next: Floating point exception running ArchiveEngine Michele Joyce
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017 
Navigate by Thread:
Prev: Re: Digitizer needed for LCLS Till Straumann
Next: RE: Digitizer needed for LCLS Liyu, Andrei
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017 
ANJ, 02 Sep 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·