1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Alarm Handler in Global mode in and outside the control room
From: "Ernest L. Williams Jr." <[email protected]>
To: Emmanuel Mayssat <[email protected]>
Cc: EPICS tech-talk <[email protected]>
Date: Fri, 14 Apr 2006 21:11:38 -0400
On Fri, 2006-04-14 at 17:09 -0700, Emmanuel Mayssat wrote:
> On Fri, 2006-04-14 at 17:30 -0400, Ernest L. Williams Jr. wrote:
> > Hi All,
> > 
> > 
> > We are able to setup the alarm handler to run in global mode in the
> > control room but want to see global acknowledgments outside the control
> > room.
> 
> global mode? Global acknoeledgement. Was is that ?

The following is from the alh User's Guide:
===============================================================================
Global Mode
The 'âglobal' options specifies that the alarm handler should run in a
global mode. In global mode an Alarm
Channel's unacknowledged severity and it's acknowledge transients state
will be determined by the current
value of the EPICS database record's ACKS and ACKT field settings. In
local mode, the default mode, the
unacknowledged severity and acknowledge transients settings are local to
the alarm handler.
===================================================================================



Maybe, I can use the "-global" flag along with the passive "-S" flag,
hmmm?

The following is again from the alh User's Guide:
==================================================================================
Passive Mode
Specifying this 'âS' option means that the alh will execute in a passive
(monitor) mode. This means that alh
can not send channel access acknowledgment of alarms and can not do
channel access puts to the
acknowledge transients fields and cannot write to the severity process
variable. It is useful for a nonâoperator
alh user.
===================================================================================


Thanks,
Ernest L. Williams Jr.
SNS Control Systems Group
ORNL


> 
> 


References:
Alarm Handler in Global mode in and outside the control room Ernest L. Williams Jr.

Navigate by Date:
Prev: Alarm Handler in Global mode in and outside the control room Ernest L. Williams Jr.
Next: Re: AlarmHandler - filtering vs. HYST Terry Carlino
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Alarm Handler in Global mode in and outside the control room Ernest L. Williams Jr.
Next: CAJ 1.0.4 issues Chu, Paul C.
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 02 Sep 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·