1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: AlarmHandler as a daemon or service
From: Michael Borland <[email protected]>
To: "Ernest L. Williams Jr." <[email protected]>
Cc: EPICS tech-talk <[email protected]>, [email protected]
Date: Thu, 23 Mar 2006 23:18:26 -0600 (CST)
Ernest,

At APS we use alh for alarm handling (to alert operators to alarms and help them investigate alarms) and sddsalarmlog for alarm logging (for archival purposes and analysis). The text log files from alh are not that convenient for postprocessing and can get rather large (though this is not a big problem now as it was during commissioning). sddsalarmlog also optionally grabs the value of a related PV when the alarm goes off, which makes it easier to figure out what happened. Since the input files to sddsalarmlog are SDDS files, much of the maintenance is automated (e.g., when PV names change or PVs are deleted). Since sddsalarmlog is not dependent on a GUI, we start/restart it with a cron job so it is "guaranteed" to always be running.

We have a Tcl/Tk application that allows analysis of sddsalarmlog output, giving time histograms, alarm history, alarm counts per PV, alarm overlap analysis, status word decoding, etc.

--Michael

---------------------------------------------------------------------
| Michael Borland, Ph. D. | Bldg 401/B2201 |
| Senior Scientist | 9700 S. Cass Avenue |
| APS Operations Division | Argonne, IL 60439 | | Argonne National Laboratory | |
| [email protected] | (630) 252-4205 office |
| | (630) 252-5703 FAX |
---------------------------------------------------------------------
http://www.aps.anl.gov/asd/oag/oaghome.shtml


On Thu, 23 Mar 2006, Ernest L. Williams Jr. wrote:

Hi everyone,

Two questions:

(1) How many sites used the EPICS AlarmHandler.

(2) Has anyone changed the EPICS AlarmHandler to run in daemon mode or
as a service?

This would be a useful mode when the logging option is used.

So, basically we would need a commandline option to enable this and give
us an alhLogger, ah?




Thanks, Ernest L. Williams Jr. SNS Control Systems Group ORNL



Replies:
Re: AlarmHandler as a daemon or service Ernest L. Williams Jr.
References:
AlarmHandler as a daemon or service Ernest L. Williams Jr.

Navigate by Date:
Prev: Re: AlarmHandler as a daemon or service Matthias Clausen
Next: Re: AlarmHandler as a daemon or service Ernest L. Williams Jr.
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: AlarmHandler as a daemon or service Maren Purves
Next: Re: AlarmHandler as a daemon or service Ernest L. Williams Jr.
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 02 Sep 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·