1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: Cost effective solution for monitoring a large number of temperatures
From: "Elder Matias" <[email protected]>
To: <[email protected]>
Date: Fri, 20 Jan 2006 11:08:26 -0600
Josh,

At the CLS we have generally standardised on 3-wire RTD sensors for most
temperature measurements.  For low-speed and high-resolution monitoring
we use National Instruments FieldPoint.  We have some thermocouples in
older parts of the facility also using FieldPoint.  The driver also
supports Relay, Digital and +/- 5V modules.

The EPICS RS-232 driver for FieldPoint was written about five to six
years ago and pre-date the existing of ASYN.  They are built on a
generic RS-232 driver library that supports RTEMS and Linux based IOCs.


We need higher speed or fast closed loop control we use PLCs or VME
cards.

IF you are interested I can send you the design note.

http://sine.ni.com/nips/cds/view/p/lang/en/nid/1206

Elder
----------

To: TechTalk EPICS <[email protected]> 
Subject: Cost effective solution for monitoring a large number of
temperatures 
From: Josh Stein <[email protected]> 
Date: Thu, 19 Jan 2006 09:03:26 -0600 
In-reply-to: <BFF4143C.9B27%[email protected]> 
References: <BFF4143C.9B27%[email protected]> 
User-agent: Mozilla Thunderbird 1.0.7 (Windows/20050923) 
Controls experts,

In the undulator hall of the LCLS we expect to monitor (what I consider)
a large number of temperature points (on the order of about 300). My
past experience with thermocouples has been local installations of
between one and eight data points. It would be easy to just scale that
solution by a factor of 40, but I have to believe there are more cost
effective solutions.

Can anyone with experience in this regard please point me in the right
direction? I'm looking for hardware that is, of course, EPICS compliant.


Thanks,
<josh>


Navigate by Date:
Prev: synApps workshop part 2 - 20-23 February Rees, NP (Nick)
Next: ASYN Question John Dobbins
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Cost effective solution for monitoring a large number of temperatures Josh Stein
Next: RE: Cost effective solution for monitoring a large number of temperatures Mark Rivers
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024