1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: environmental variables
From: "Jeff Hill" <[email protected]>
To: "'Xu HuiJuan'" <[email protected]>, <[email protected]>
Date: Mon, 28 Nov 2005 09:07:22 -0700

> -----Original Message-----
> From: Xu HuiJuan [mailto:[email protected]]
> Sent: Sunday, November 27, 2005 5:54 PM
> To: [email protected]
> Subject: environmental variables
> 
> I know what happened.
> I added three environmental variables:
> EPICS_CA_ADDR_LIST           the address I want to link
> EPICS_CA_AUTO_ADDR_LIST      NO
> EPICS_CA_SERVER_PORT         8888
> After I deleted these variables, the CA_Get can link my own soft IOC.
> But I want to link the IOC data on another PC. What is the right
> environmental variables?
> Thanks!

Following the tradition of computer support personnel everywhere I will
answer a question - with another question :-]

That depends on the address of the IOC that you wish to connect to!

1) If the soft IOC is on the same IP subnet as the client then you can set
EPICS_CA_AUTO_ADDR_LIST=YES and not set EPICS_CA_ADDR_LIST (this is the
default).

2) If it is on a different IP subnet then set EPICS_CA_ADDR_LIST to the
broadcast address of the soft IOC's subnet (if your routers are configured
to permit this) or to the IP address of the host that you wish to connect
to.

The proper value for EPICS_CA_SERVER_PORT should be the same port number
that you have configured the server in your soft IOC to use (the default is
5064).

The CA reference manual can also be consulted concerning these issues.

Jeff


References:
environmental variables Xu HuiJuan

Navigate by Date:
Prev: Re: EDM on Windows + Hummingbird? Kay-Uwe Kasemir
Next: Re: Using subArray Carl Lionberger
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: environmental variables Ralph Lange
Next: ASYN command string with null character Bruins, Stefan
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 02 Sep 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·