Hi Hasan,
> I'm new in EPICS. I tried to write a sequence program.
> Everything worked fine but when i wanted to load the sequence
> program from my VxWorks IOC then I'm getting the following
> error messages .....
>
> seq rftfExample, "user=test"
> SEQ Version 2.0.10: Mon Jan 31 20:22:58 2005
> Illegal magic number in state program.
> - Possible mismatch between SNC & SEQ versions
> - Re-compile your program?
> value = 0 = 0x0
Are you using vxWorks, and the vxWorks shell?
If so, then the syntax of the command you need to use is:
seq &rftfExample, "user=test"
i.e. you need the "&" (address-of) operator before the name of the
program.
Mark