The problem is not with EPICS. The ethernetIP device support code explicitly
sets LINR to 0 during init.
John Sinclair
On Monday 20 December 2004 5:57 pm, you wrote:
> For R3.14.6, ai record, the following:
>
> field(LINR, "LINEAR")
>
> does not generate a database parse error, but after iocInit the LINR field
> is set to 0 and the behavior of the record seems to be independent of the
> value of ESLO.
>
> Poking a 2 into LINR seems to make the record aware of the ESLO field.
>
> Can anyone explain this. I've read the record manual but am still not
> certain of the correct value for the LINR field.
--
John Sinclair
- References:
- database conversion john sinclair
- Navigate by Date:
- Prev:
Re: database conversion Andrew Johnson
- Next:
Re: Index of highest value Tim Mooney