1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE:Thales RF transmitter controls
From: "Elder Matias" <[email protected]>
To: "Chris Timossi" <[email protected]>
Cc: <[email protected]>, "Glen Wright" <[email protected]>, "Robby Tanner" <[email protected]>
Date: Tue, 23 Nov 2004 08:13:13 -0600
Chris,

At CLS we have a Thales system.  In our design we had Thales use a
Siemens S7/400 PLC.  This was because we were integrating this into an
RF system with a supper conducting RF cavity where the process control
on the cavity and the low level RF was being done using Siemens PLC
hardware and there was a need for some data sharing between the three
systems.   Profibus is used as the data network between the PLCs.

At the time we had the choice of using the design Thales had done with
the SLS using a VME/PowerPC based IOC instead of the PLC.  For us with
the type of cavity and low level RF design we were planning the PLC
option was the best fit.  If you are using a room temperature cavity and
have PowerPC based IOCs the SLS system may be a better fit for you.

We used a DIN rail mounted PC from Kontron (formally Pep Modular) that
contains a Profibus card (PC/104 form factor) to do the interface
between EPICS and the RF system.  

If you would like additional information, Glen Wright wrote the Profibus
driver and Robby Tanner has done the PLC programming.

Elder Matias
Canadian Light Source Inc.


--------------------------
To: [email protected] 
Subject: Thales RF transmitter controls 
From: Chris Timossi <[email protected]> 
Date: Mon, 22 Nov 2004 09:15:37 -0800 
Organization: Lawrence Berkeley National Laboratory 
User-agent: Mozilla/5.0 (Windows; U; Windows NT 5.1; en-US; rv:1.7.1)
Gecko/20040707 

Has anyone had experience controlling a Thales transmitter for their RF
systems with EPICS? I understand that they can be ordered with emedded
PLCs that may have an Ethernet interface.


Chris Timossi
Advanced Light Source,
Berkeley, CA, USA



Navigate by Date:
Prev: RE: only 16 enum states? Liyu, Andrei
Next: RE: only 16 enum states? Jeff Hill
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: Thales RF transmitter controls Owens, PH (Peter)
Next: RE: Thales RF transmitter controls Gurd, Pamela A.
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·