1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: EtherNet/IP for AB SLC5/05 PLC.
From: john sinclair <[email protected]>
To: Kay-Uwe Kasemir <[email protected]>, Kiman Ha <[email protected]>
Cc: [email protected]
Date: Mon, 8 Mar 2004 11:59:41 -0500
Kay,

Is this also true for FlexLogix I/O?

John Sinclair

On Monday 08 March 2004 11:13 am, Kay-Uwe Kasemir wrote:
> On 2004.03.08 02:24, Kiman Ha wrote:
> > Hello! Kay and Stephanie,
> > Last Feb, I asked about AB SLC5/05 processor for Ethernet TCP/IP EPICS
> > driver and support.
> > The AB Comapny people said SLS5/05 PLC processor support EtherNet/IP.
>
> Yes, it might support the common portion of the EtherNet/IP
> protocol, the part that's documented at www.odva.org.
>
> That will allow you to read the serial number of your SLC5/05's
> ethernet interface.
>
> In addition, you need the CIP service codes that are specific
> to your PLC, the ones that allow you to read/write tags
> or files or whatever the data of interest is called on the
> respective architecture.
>
> > I known your alread developed EtherNet/IP drivers and support for SNS
> > project.
>
> That EtherNet/IP driver package uses the CIP codes for the
> AB ControlLogix 5000 series as described in
> AB Publication 1756-RM005A-EN-E.
>
> The latter publication also lists SCL commands,
> but they are very different from the CIP service codes
> for the ControlLogix series.
> Control Logix uses CIP service codes
> 0x4C : read data
> 0x4D : write data
> 0x0A : multi request
> and all those adress string tags on the Logix5000.
>
> As far as I know, the SCL5 doesn't have string tags
> but uses file/element/subelement addressing.
>
> So I'm afraid those AB people who talked to you can
> recite "EtherIP" from some SLC5 brochure but don't
> really understand the protocol.
>
> This means that the ether-ip driver for the ControlLogix 5000 won't
> talk to the SLC5, and making it talk to the SLC5 would be a major deal,
> close to starting from scratch.

-- 
John Sinclair


Replies:
Re: EtherNet/IP for AB SLC5/05 PLC. Kay-Uwe Kasemir
References:
EtherNet/IP for AB SLC5/05 PLC. Kiman Ha
Re: EtherNet/IP for AB SLC5/05 PLC. Kay-Uwe Kasemir

Navigate by Date:
Prev: Re: [Fwd: LabView/EPICS] W T Meyer
Next: Re: [Fwd: LabView/EPICS] Kay-Uwe Kasemir
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: EtherNet/IP for AB SLC5/05 PLC. Kay-Uwe Kasemir
Next: Re: EtherNet/IP for AB SLC5/05 PLC. Kay-Uwe Kasemir
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·