1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: CA conversion problem
From: "Eric Boucher" <[email protected]>
To: "Tech-Talk" <[email protected]>
Date: Thu, 19 Feb 2004 18:59:35 +0100
Hi Folks,

I've a problem when requesting DBR_CTRL_XXX types with channel access.
If I request a DBR_CTRL_FLOAT and that one of the limit (Upper display,
Lower display, etc...) is 0 then instead of getting 0 and
get -1.17549435E-38.
If I request any other DBR_CTRL_XXX types then I get the correct value.
Is it a bug in the CA convertion routine?

Thanks,
Eric

----------------------------------

TYPE: DBR_CTRL_FLOAT
COUNT: 1
VALUE: 0.0
STATUS   : LOLO_ALARM
SEVERITY : MAJOR_ALARM
PRECISION: 0
UNITS    : Counts
UDL      : 10.0
LDL      : -1.17549435E-38
UAL      : 8.0
UWL      : 6.0
LWL      : 4.0
LAL      : 2.0
UCL      : 10.0
LCL      : -1.17549435E-38

TYPE: DBR_CTRL_DOUBLE
COUNT: 1
VALUE: 0.0
STATUS   : LOLO_ALARM
SEVERITY : MAJOR_ALARM
PRECISION: 0
UNITS    : Counts
UDL      : 10.0
LDL      : 0.0
UAL      : 8.0
UWL      : 6.0
LWL      : 4.0
LAL      : 2.0
UCL      : 10.0
LCL      : 0.0

TYPE: DBR_CTRL_INT
COUNT: 1
VALUE: 9
STATUS   : HIHI_ALARM
SEVERITY : MAJOR_ALARM
UNITS    : Counts
UDL      : 10
LDL      : 0
UAL      : 8
UWL      : 6
LWL      : 4
LAL      : 2
UCL      : 10
LCL      : 0



Replies:
Re: CA conversion problem Marty Kraimer

Navigate by Date:
Prev: ai setting ROFF Pauline
Next: Re: CA conversion problem Marty Kraimer
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: ai setting ROFF Pauline
Next: Re: CA conversion problem Marty Kraimer
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·