1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: PV reconnect logic question
From: "Jeff Hill" <[email protected]>
To: "'Kevin Tsubota'" <[email protected]>, "'tech-talk \(E-mail\)'" <[email protected]>
Date: Mon, 12 Jan 2004 08:41:18 -0700
Kevin,

Your Solaris-8 IOC (acting as a client) probably does not see the server's
beacons because they are addressed to subnet on which your client IOC is not
listening. The EPICS R3.14 CA reference manual explains this situation in
more detail than in past versions of the manual. See the section entitled
"Dynamic Changes in the CA Client Library Search Interval".

It may be that a simple solution will be to expand the server's beacon
address list so that beacons are broadcasted also on your Solaris-8 IOC's
subnet. Alternatively, you could install a CA gateway providing transparent
connectivity for remote clients.

Jeff

> -----Original Message-----
> From: Kevin Tsubota [mailto:[email protected]]
> Sent: Friday, January 09, 2004 6:02 PM
> To: tech-talk (E-mail)
> Subject: PV reconnect logic question
> 
> 
> Hi,
> 
> I have EPICS R3.14.1 IOC running on Solaris-8 and it connects to EPICS
> R3.13.0b12 PVs running
> under VxWorks.  As an interim safety measure I disconnect the routes
> between
> the two IOCs at
> night and reconnect them during the day.
> 
> However when I reestablish the routes, my R3.14 IOC PV never reconnects
> to
> the VxWorks PVs.
> It stays in STAT=LINK, SEVR=INVALID state.  THe R3.14 PV is using a CPP
> input link to the
> VxWOrks PV.  When I restart my R31.4 IOC it connects up right away.
> 
> Why doesn't the R3.14 PV reconnect automatically?
> Is there a way to force the R3.14 PV to reconnect without having to
> restart
> it?
> 
> Mahalo!
> 
> Kevin Tsubota
> W.M. Keck Observatory



References:
PV reconnect logic question Kevin Tsubota

Navigate by Date:
Prev: Re: Implementation of alarm handlers by EPICS users Kate Feng
Next: Re: Choice of Power PC VME cards Andrew Johnson
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: PV reconnect logic question Ernest L. Williams Jr.
Next: RE: PV reconnect logic question Kevin Tsubota
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  <20042005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·