1994  1995  1996  1997  1998  1999  2000  2001  2002  <20032004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  <20032004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Alarm box (wasalarm box (was any solution besides the TVs and alarm handler ?)
From: Noel Giffin <[email protected]>
To: Maren Purves <[email protected]>
Cc: Kate Feng <[email protected]>, [email protected]
Date: Tue, 17 Jun 2003 19:10:53 -0700


Maren Purves wrote:
Kate Feng wrote:

Hi all,

[...]


Does anyone (or Garrett) know of an alarm box consisting of a buzzer,

bell, horn,  or siren, lights  and sirens that is commercially available
and
could be drivern by  a VME bit outputs?


Kate,

I meant to reply to tech-talk in March when this first came up but found
that I didn't and didn't bother afterwards. Our alarm handler setup looks
like this:
(this is one of several)

GROUP NULL uist
$SEVRCOMMAND UP_MINOR echo "UIST temperature exceeds 34K" | /usr/ucb/mail -s "UIST temp. exceeds 34K" maren-uist
$SEVRCOMMAND UP_MAJOR echo "UIST temp. exceeds 35K" | /usr/ucb/mail -s "UIST temp. exceeds 35K" maren-uist
$SEVRCOMMAND UP_INVALID echo "UIST temp. invalid" | /usr/ucb/mail -s "UIST temp invalid" maren
CHANNEL uist uistTmp:330:cdat


we don't use the alarm handler screen at all, it is on a monitor in a corner
that hardly anybody ever looks at. We here decided on using email for alarm
notification, it was talked about pager software at some point, but decided
against it. One way or the other we needed a solution that works remotely
as there is nobody at the telescope about half the time.


Of course you don't have to send email in your setup, but you can put in
any command. If you can find any kind of alarm box that does whatever you
want it to do you can command it via the alarm handler - and ignore the
alarm handler's own user interface as well as whether your alarm box can
be driven by VME bit outputs.


Maren


We've built a Ion Beam Radiation monitoring system here at TRIUMF
for the ISAC facility that uses local area flashing beacons and audible
alarms using standard commercial systems from Patlite.

We trigger them with a 24 volt isolated relay signaled from a
VMIC VME digital output module.

I'm not sure if this is the sort of thing you were looking for.

Regards,
Noel Giffin
TRIUMF Safety Systems


References:
Alarm box (wasalarm box (was any solution besides the TVs and alarm handler ?) Kate Feng
Re: Alarm box (wasalarm box (was any solution besides the TVs and alarm handler ?) Maren Purves

Navigate by Date:
Prev: Re: Alarm box (wasalarm box (was any solution besides the TVs and alarm handler ?) Maren Purves
Next: Building EPICS R3.14.2 under Windows Ernest L. Williams Jr.
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  <20032004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Alarm box (wasalarm box (was any solution besides the TVs and alarm handler ?) Maren Purves
Next: medm valuator increment Kate Feng
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  <20032004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·