Hi Bill,
It looks like the stringin record never posts monitors if the value has not changed.
A couple of options:
- Make a simple database where the stringin record forward links to another record that does post monitors every time it processes. You can put a monitor on that record, and whenever it posts an event then you know the stringin record has received new input, so you can read it.
- Use my generic serial record http://cars9.uchicago.edu/software/recSerial.html
which always posts monitors on new input. It only works with mpfSerial device support, however.
Mark Rivers