EPICS Controls Argonne National Laboratory

Experimental Physics and
Industrial Control System

1994  1995  1996  1997  1998  1999  2000  2001  2002  <20032004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  <20032004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Agilent E2050B LAN/GPIB gateway no longer available
From: "Allison, Stephanie" <[email protected]>
To: "'[email protected]'" <[email protected]>
Date: Tue, 07 Jan 2003 18:01:46 -0800
Hello,

I'm testing the Agilent E5810A LAN box on an 3.14/RTEMS and 3.14/vxWorks IOC.
The E5810A will not reboot when requested by drvHpGpibConfig (pre-iocInit link configuration).  Unlike the 2050A/B, the reboot is password-protected on the E5810A.  Without the reboot, I must  manually reboot the LAN box before rebooting my IOC.  If I don't, the third time my IOC reboots, and forever after, I get this: 

drvHpGpibConfig(2,"ip_address_deleted",0,3000,"gpib0")
drvHpE2050AGpib (release 1.0) initialized successfully
drvGpib (release 3.0) initialized successfully
drvGpibLinkTask(gpib00002): started
RTEMS:
hpGenLink(0x1c59178): can't connect to gateway: No more processes
vxWorks:
hpGenLink(0xf8c8b0): can't connect to gateway: S_errno_ETIMEDOUT
drvGpibLinkStart(0x1c59178): linkTask init failure / timeout
   
Has anyone (Noboru?) solved this problem yet?  

Thanks for any response,

Stephanie Allison
SSRL/Spear Controls

>From Sep 2002 archives:

>We have tested E5810A with EPICS E2050B support and confirmed it works with
>it. You may need to change a startup script or setting of E5810A, though.
>The default "GPIB SICL Interface name" on
>HP2050A is "hpib" whereas it on HP5810A is "gpib0".
>After changing "hpib" in drvHpGpibConfig command in the startup script
>to "gpib0". EPICS software can establish the link and can control GP-IB
>devices under the LAN-GPIB box, HP5810A. We are going to test the HP
>5810A in more detail.
>
>Regards,
>
>Noboru Yamamoto
>EPICS group/KEKB control Group
>KEK, JAPAN



Navigate by Date:
Prev: a question about edm 黄松
Next: _excStub & _excIntStub Owens, PH (Peter)
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  <20032004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: a question about edm 黄松
Next: _excStub & _excIntStub Owens, PH (Peter)
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  <20032004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·