EPICS Controls Argonne National Laboratory

Experimental Physics and
Industrial Control System

1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: alarm handler
From: john sinclair <[email protected]>
To: Marty Kraimer <[email protected]>
Cc: tech talk <[email protected]>
Date: Wed, 14 Aug 2002 11:00:07 -0400 (EDT)
I see in alh the following code:

  status = ca_put(DBR_PUT_ACKS, chid, psevr);

but alh does not seem to affect the ACKS field of a pv
which explains why two instances of alh are not necessarily
in sync with respect to the acknowledged state of a pv.

Is this the result of improper configuration on my part?

We are not currently using access security at all.

John

On Wed, 14 Aug 2002, Marty Kraimer wrote:

> 
> 
> john sinclair wrote:
> 
> > Can the ACKS and ACKT fields be modified via
> > channel access? When I try, ca_put fails.
> > 
> > John Sinclair
> > [email protected]
> > Oak Ridge National Lab
> > 865-576-6362   865-574-1268 (fax)
> > 
> > 
> 
> 
> 
> ACKS can only be changed via a DBR_PUT_ACKS request.
> 
> ACKT can only be changed via a DBR_PUT_ACKT request.
> 
> 
> 
> ACKS,ACKT are present for alarm handlers not general purpose CA clients.
> Note that access security can be used to limit who/where/when can modify these 
> fields.
> 
> Marty Kraimer
> 
> 
> 

John Sinclair
[email protected]
Oak Ridge National Lab
865-576-6362   865-574-1268 (fax)


Replies:
Re: alarm handler Ralph . Lange

Navigate by Date:
Prev: RE: Passing large arrays over channel access with R3.14b2 Jeff Hill
Next: Re: alarm handler Ralph . Lange
Index: 1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: alarm handler john sinclair
Next: Re: alarm handler Ralph . Lange
Index: 1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·