1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: AO Record: New Drive Limit Mode?
From: Kay-Uwe Kasemir <[email protected]>
To: [email protected]
Date: Tue, 09 Apr 2002 09:27:16 -0600
Hello:

Some users here at LANL had a suggestion that's actually useful.
The best solution seems to be a new AO record field,
but before adding it, Marty suggested to run the idea by the
community. His concerns:

1) Is it compatible with existing applications? VERY important.
Definitely: Default behavior of AO stays the same.
When new field is added to the "end" of the other AO fields,
driver/device support is binary compatible(!) with original AO.
Otherwise recompilation is required.

2) Are these new fields generally useful?
I'd say so.

3) Are there other ideas that will accomplish the same purpose
   but provide even more functionality with about the same overhead.
I'll list some, but none look compelling to me.

The problem is about entering "wrong" values from a GUI,
that is values outside of [DRVL, DRVH].
Per default, the AO record would "clamp" the value, e.g.
Value > DRVH    ==>   value = DRVH.

This can lead to jumps. Example: [DRVL,DRVH]=[0...10], current value 0.5.
User wants to make it 0.6 but accidentally enters 60
==> You jump to 10. That's a big jump from 0.5!
Just staying at 0.5 and allowing the user to try again
might be better.

It's little things like this which make people
(at least here at LANL) say: EPICS stinks, this would be
so easy to do in LabVIEW, Visual Basic, Fortran, anything else.

Marty suggested that OROC weakens the "jump". True,
but it is confusing to the user when he enters a
something outside the limits and suddenly the value
starts ramping towards the high/low end.

Solution: New AO field DRLM - "Drive Limit Mode"
Possible Values:

a) "Clamp" (default)
As before, any value outside of DRVL ... DRVH
is clamped/changed to DRVL or DRVH.

b) "Reject"
Any value outside of DRVL ... DRVH
is rejected. The record returns to the
previous value (still available in the OVAL field).

Alternatives to this solution are:
a) Don't modify the "original" AO but create a new "MyAO".
   ==> Have to add new device support DBD entries.
b) Replace each GUI-related AO record by a combination of AO, CALCOUT
   that performs the checking.
   ==> Much more CPU overhead: Multiple records instead of ~5 lines of C.
c) AO record for GUI, AO record for the value that's actually used,
   SNL sequence that handles the checking.
   ==> Like b but worse


Thanks,
-Kay

PS: Here are the diffs from R3.13.5 that implement DRLM:

Index: aoRecord.dbd
===================================================================
4a5,10
>
> menu(aoDRLM) {
>       choice(aoDRLM_Clamp,"Clamp")
>       choice(aoDRLM_Reject,"Reject")
> }
>
105a112,119
>
>       field(DRLM,DBF_MENU) {
>               prompt("Drive Limit Mode")
>               promptgroup(GUI_OUTPUT)
>               interest(1)
>               menu(aoDRLM)
>       }
>                                          

Index: aoRecord.c
===================================================================
96a97,99
> #define DRLM_Clamp 0
> #define DRLM_Reject 1
>
475,479c478,498
<         /* check drive limits */
<       if(pao->drvh > pao->drvl) {
<               if (value > pao->drvh) value = pao->drvh;
<               else if (value < pao->drvl) value = pao->drvl;
<       }
---
>     /* check drive limits */
>     if(pao->drvh > pao->drvl)
>     {
>         /* Clamp  => Force to be within DRVL ... DRVH
>          * Reject => Revert back to old value unless within limit
>          */
>         if (value > pao->drvh)
>         {
>             if (pao->drlm == DRLM_Clamp)
>                 value = pao->drvh;
>             else
>                 value = pao->oval;
>         }
>         else if (value < pao->drvl)
>         {
>             if (pao->drlm == DRLM_Clamp)
>                 value = pao->drvl;
>             else
>                 value = pao->oval;
>         }
>     }


Replies:
Re: AO Record: New Drive Limit Mode? J. Frederick Bartlett ([email protected])
Re: AO Record: New Drive Limit Mode? Andrew Johnson

Navigate by Date:
Prev: RE: seq 1.9.4 Ned Arnold
Next: Re: AO Record: New Drive Limit Mode? J. Frederick Bartlett ([email protected])
Index: 1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: PCAS for WIN32 Graham Waters
Next: Re: AO Record: New Drive Limit Mode? J. Frederick Bartlett ([email protected])
Index: 1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·