It sounds like there is a problem with the communication between the DCM and
your IOC.
Do the following (All via the vxWorks shell)
dbpf "<dcm record>.TPRO","1"
What does it show? Does it show active for 8 seconds spans? I will guess yes.
Now type
dbior "drvAb",3
On the link that has the DCM look at the first part. You should see something
like:
AB-6008SV link: 1 osw 002c vme: 0xf0c01000
6008SV2R Scanner Series A Revision A Copyright (c) 1995 Allen-Bradley
Company
Mailbox lock timeouts 0
Command timeouts 1
Command Failure 0
Interrupts per second 13
Block Transfers per second 6
Adapter Status Words
1f20 0000 0000 0000 1d20 0000 0000 0000
0000 0000 0000 0000 0000 0000 0000 0000
0000 0000 0000 0000 0000 0000 0000 0000
0000 0000 0000 0000 0000 0000 0000 0000
scan list
00 04
Adapter 0 ONLINE 1 slot addressing
CARD 0: BT Scanning abDcm
Do you see an excessive number of command timeouts and/or failures?
Also do a
dbpr "<dcm record>",3
dbpr "<bi record>",3
Where <bi record> is the record you are looking at on the dm2K screen.
I would like to see these.
Marty Kraimer
Zheng Lifang wrote:
>
> Dear all,
>
> I have been testing a Protecting System similar to APS's, which has three levels. The first is a VME crate plugged with a MVME2302/IOC, a SV2R6008 scanner. The second is a AB crate plugged with a 1771DCM, a PLC5/40, a 1771SDN and two I/O local modules. The third is a 1794ADN which controls a 1794IB16 & a 1794OB16.
> The first success should contribute to much help from Prof.M.Kraimer, Dr.A Johnson and Dr.
>
> Now I meet some other questions. I use Rockwell RSlogix 4.11.00 revision to program PLC.
>
> local input: I:010
> DCM read buf: N10:0
> DCM write buf: N10:64
> SDN read buf: N11:0
>
> When PLC sends data(block transfer) to DCM, the tag is set to 0 or 1 to distinguish the data from local I/O or from DeviceNet FlexI/O.
>
> The rung orders are:
>
> copy I:010 to N10:66
> set N10:65=0 (tag=0)
> BTW to DCM (l=64)
> BTR read data to N11:0 from DeviceNet(l=62)
> copy N11:1 to N10:66
> set N10:65=1 (tag=1)
> BTW to DCM
>
> I use DM2K to display and there occur two problems.
> 1)Occasionally there is some exchanging data between local I/O and DeviceNet I/O.
> 2)When I change the local or FlexI/O input module states, there is unbearable delay in DM2K to update. When I use .5second to process abDCM record, the delay is nearly 8 seconds.
>
> Any suggestion is welcome.
>
> Lifang
- References:
- Ladder logic programing for PLC Zheng Lifang
- Navigate by Date:
- Prev:
Ladder logic programing for PLC Zheng Lifang
- Next:
An et_wish crash Andy Foster
- Index:
1994
1995
1996
1997
1998
1999
2000
<2001>
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Ladder logic programing for PLC Zheng Lifang
- Next:
An et_wish crash Andy Foster
- Index:
1994
1995
1996
1997
1998
1999
2000
<2001>
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
|