EPICS Controls Argonne National Laboratory

Experimental Physics and
Industrial Control System

1994  1995  1996  1997  1998  1999  2000  <20012002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  <20012002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: How to monitor 700 thermocouples?
From: Matthew Rippa <[email protected]>
To: "Rarback, Harvey" <[email protected]>, EPICS tech-talk <[email protected]>
Date: Thu, 16 Aug 2001 12:39:22 -1000
Hi Harvey,

We have almost 250 (4-wire)RTD's connected to 3 Keithley 7002 switch boxes 
(10, 10 channel cards ) with a Keithley 2010 DMM taking measurments.  The 
crates are about $3800 each and the DMM was about $2400.  That puts you in 
the ~$42 per sensor range for 7 crates and 1 DMM.  We also added an HP 
LAN/GPIB gateway for $400 I think.

EPICS records are assigned to each sensor and we scan the entire loop in 
under 3 minutes.  You could decrease this time by increasing the number of 
DMM's.  That puts you up to the ~$62 per sensor range for a DMM per crate.
Hope this helps.

Regards,
Matt

On Wednesday 15 August 2001 07:54, Rarback, Harvey wrote:
> Folks,
>
> We need to monitor about 700 thermocouples for the SPEAR3 upgrade.  There
> will be about 40 TCs on 18 girders distributed around the 230m ring
> circumference. The present plan is to monitor the temperatures at a few
> second intervals.  We have a couple of quotes from PLC vendors, but they
> are fairly expensive.
>
> Does anyone have a suggestion for hardware and software to accomplish our
> task?  Of course the aim is to get the temperatures into an IOC.
>
>                                    --Harvey
>    ----
> Harvey Rarback                        phone:      (650)926-3963
> Stanford Linear Accelerator Center    fax:        (650)926-4100
> 2575 Sand Hill Road                   home phone: (650)560-9111
> Menlo Park, CA 94025
> [email protected]


References:
How to monitor 700 thermocouples? Rarback, Harvey

Navigate by Date:
Prev: Re: RAWF, RAWL Andrew Johnson
Next: Re: An additional remark on C++ Chip Watson
Index: 1994  1995  1996  1997  1998  1999  2000  <20012002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: How to monitor 700 thermocouples? Maren Purves
Next: An additional remark on C++ Benjamin Franksen
Index: 1994  1995  1996  1997  1998  1999  2000  <20012002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·