1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Fast Ethernet and Baja
From: Alastair Borrowman <[email protected]>
To: "Tech-Talk (E-mail)" <[email protected]>
Date: Thu, 27 Apr 2000 17:23:41 +0100
Hi,
I'm trying to get a HK Baja4700 to use a Digital Fast EtherWorks/PMC Adapter
(DE520-AA) network interface card. Does anybody have experience of this
combination?

What I've done so far:

Plugged the fast Ethernet card into Baja PMC expansion site -J1x (Jumper  J1
is removed to select IEEE-802.3 Ethernet protocol).

And watched the following be displayed on a console connected to the Baja:

Baja power up tests passed
.
.
.

VEND  DEV  REV  BASE0     BASE1     BASE2  BASE3  BASE4  BASE5
1011  9    22   30000000  20000000  ....   ....   ....   ....

...Some stuff about Heurikon Baja

boot device: ei
processor number: 0
.
IP addresses and
more boot stuff for vxWorks 5.3
.
.

Mapping RAM base to A32 space at 0x40000000... done
Waiting for VME /SYSFAIL to clear... done
Attaching network interface ei0... done
Attaching network interface lo0... done
Loading...

Waiting long enough the following is displayed and the vxWorks boot prompt
appears:
Error Loading File: errno 0x3c (timeout)

When the Baja's built-in Ethernet socket is used the loading continues
normally and all progresses well (using the same boot parameters).

The green led on the fast Ethernet card is lit, showing it is connected to
an active network, but the activity led, showing an RX or TX in process,
never lights.

I've used the vxWorks Boot prompt command 'd' to read the address 0x1f01000
which shows bit 4=0, indicating that PMC site J1x is occupied (bit 5=1,
showing J2x is empty).

Obviously I've missed something, does anybody have any ideas at to what it
may be?

Thanks in advance,
Alastair Borrowman


Navigate by Date:
Prev: Re: Hardware to for thermocouple readout Steve Lewis
Next: aao record behaviour Korhonen Timo
Index: 1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: Hardware to for thermocouple readout Mark Rivers
Next: aao record behaviour Korhonen Timo
Index: 1994  1995  1996  1997  1998  1999  <20002001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·