Jennifer Dunn wrote:
>
> Hi,
>
> I am creating a custom record, and have defined a field in the record to
> have special processing at run time (special = SPC_MOD) and have the pp_value
> set to YES (a passive record should be processed when Channel Access writes
> to this field).
>
> In the record support code I have a routine called special, that simple sets
> a flag to indicate that the record was accessed - and then expect that
> after special the "process" routine should be called.
process is not called as a result of a put to a special field.
If you want the record processed then, after the second call to special, call
scanOnce.
Marty Kraimer