1994  1995  1996  1997  <19981999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  <19981999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: RE: increasing scan rates
From: [email protected] (Jeff Hill)
To: "'Geoff Savage'" <[email protected]>, "[email protected]" <[email protected]>
Date: Fri, 14 Aug 1998 13:29:42 -0600
On Friday, August 14, 1998 1:14 PM, Geoff Savage [SMTP:[email protected]] wrote:
> Hi,
> 
> Is it possible to increase the scan rate to greater than 10 Hz (.1 second)?
> 

Higher scan rates can be obtained by configuring the record's SCAN field to 
"I/O Interrupt" or "Event". The former causes the record to be processed
when device support calls scanIoRequest(), and the latter causes the record
to be scanned when some application program calls post_event().

Jeff


Navigate by Date:
Prev: Re: MBBI, SHFT, and GDCT Andy Foster
Next: RE: increasing scan rates Peregrine McGehee
Index: 1994  1995  1996  1997  <19981999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: increasing scan rates Geoff Savage
Next: RE: increasing scan rates Peregrine McGehee
Index: 1994  1995  1996  1997  <19981999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·