1994  1995  1996  1997  <19981999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  <19981999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Xycom 566 waveform
From: [email protected] (Garrett D. Rinehart)
To: [email protected]
Date: Wed, 17 Jun 1998 14:45:30 -0500
Hello again everybody.

I'm back to trying to read a waveform with a Xycom 566, but this time I'm doing it
the normal (one channel) way.  This is a grep on my source directory to show which
Xy566 items I've included and which I have not:

base.dbd:device(ai,VME_IO,devAiXy566Se,"XYCOM-566 SE Scanned")
base.dbd:#device(ai,VME_IO,devAiXy566Di,"XYCOM-566 Dif Scanned")
base.dbd:#device(ai,VME_IO,devAiXy566DiL,"XYCOM-566 Dif Latched")
base.dbd:device(waveform,VME_IO,devWfXy566Sc,"XYCOM-566 Single Channel")
base.dbd:driver(drvXy566)
baseLIBOBJS:#LIBOBJS += $(EPICS_BASE_BIN)/devAiXy566Di.o
baseLIBOBJS:#LIBOBJS += $(EPICS_BASE_BIN)/devAiXy566DiL.o
baseLIBOBJS:LIBOBJS += $(EPICS_BASE_BIN)/devAiXy566Se.o
baseLIBOBJS:LIBOBJS += $(EPICS_BASE_BIN)/devWfXy566Sc.o
baseLIBOBJS:LIBOBJS += $(EPICS_BASE_BIN)/drvXy566.o

With this, a board set up for ai operation works fine, but the one set up for
waveform won't even initiallize. The normal ai board is set up for A16=0x6000,
A24=0x000000. The WF board is set up with A16=0x9000, A24=0x080000. Also note that
"ai_xy566_io_report" returns one active Xycom set up for ai. "xy566_io_report"
returns nothing. Also note that the ai board is initiallized even with no ai records
loaded, while the wf is never initiallized. 

I have but two questions:
1) Can SE ai and WF coexist?
2) What am I missing?

-- Garrett Rinehart
   Intense Pulsed Neutron Source
   Argonne National Laboratory


Replies:
Re: Xycom 566 waveform Bob Dalesio

Navigate by Date:
Prev: Re: boot problems & related on hkbaja47 Maren Purves
Next: Re: boot problems & related on hkbaja47 Ned Arnold
Index: 1994  1995  1996  1997  <19981999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: boot problems & related on hkbaja47 Jeff Hill
Next: Re: Xycom 566 waveform Bob Dalesio
Index: 1994  1995  1996  1997  <19981999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·