EPICS Controls Argonne National Laboratory

Experimental Physics and
Industrial Control System

1994  1995  <19961997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  <19961997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Problem changing to use ASCII database
From: Philip Taylor <[email protected]>
To: [email protected]
Cc: Andy Foster <[email protected]>, Chris Mayer <[email protected]>
Date: Wed, 27 Mar 1996 16:41:59 +0000 (GMT)
On Wed, 27 Mar 1996, Rozelle Wright wrote:
> I'm not sure about other sites, but here at Los Alamos, all of our 
  capfast symbols
> have pproc(<for every link where it matters>) set to NPP, so the 
  change won't affect
> us at all.  I think most places using capfast got their symbols from us, so
> it should not be a real problem for capfast users.  It is a problem 
  for people
> who made their databases directly from dct.
> Rozelle
> 

Unfortunately it *has* been a real problem for this Capfast 
user - its taken quite a lot of effort to track down all the 
default PP links that were assumed in our old DCT generated 
database.

I'm not sure which Capfast EPICS symbol library is the one 
used at LANL - is it the one distributed with EPICS or by
Phase3 (or neither)?

Another added complication that has been exposed by our
changing to using a new e2sr (V2.1.3) is that the typ() 
port property defined in the symbol library for many 
fields is wrongly set to "val". e2sr now complains 
at great length about this. I think this means that the 
pproc() property is ineffective for these links. In these
cases I can only force links to be PP by setting pproc() to
be PP *and* also changing the typ() property for the 
link to "path".

Philip

------------------------------------------------------------
Philip Taylor, Royal Greenwich Observatory, 
Madingley Road, CAMBRIDGE. CB3 0EZ. UK
Email : [email protected]      Phone : (UK+) (0)1223-374710
------------------------------------------------------------


References:
Re: Problem changing to use ASCII database Rozelle Wright

Navigate by Date:
Prev: Re: Problem changing to use ASCII database Marty Kraimer
Next: Re: Problem changing to use ASCII database Rozelle Wright
Index: 1994  1995  <19961997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: Problem changing to use ASCII database Marty Kraimer
Next: Re: Problem changing to use ASCII database Rozelle Wright