EPICS Controls Argonne National Laboratory

Experimental Physics and
Industrial Control System

1994  <19951996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  <19951996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: IOC time 1min=90sec ??
From: [email protected] (Marty Kraimer)
Date: Mon, 16 Jan 1995 10:56:45 -0600
On your ioc 
1) Find out what sysClkRateGet returns
2) Call tickGet twice and manually measure the time between calls

Does (tickget2 - tickget1)/sysClkRateGet equal the time you measured?

> From [email protected] Mon Jan 16 10:44 CST 1995
> Date: Mon, 16 Jan 1995 17:46:28 EST
> From: "Gabor Csuka, DESY - Germany" <[email protected]>
> To: [email protected]
> Cc: [email protected]
> Subject: IOC time 1min=90sec ??
> Content-Type> : > text> 
> Content-Length: 841
> 
> Hi,
> 
> Our IOC -s time is after a correct syncronization working too fast.
> After 40min the time is increasd with 1 hour. Where is my failure ?
> 
> Our configuration:
> NO hardware clock, NO NTP server
> 
> 1 ioc:
> TSconfigure (1, 10, 60, 0, 0)
> -> TSreport
> Soft timing slave
> Master timing IOC alive
> Time protocol sync with unix
> Clock Rate in Hertz = 60
> Sync Rate in Seconds = 10
> Master communications port = 18323
> Slave communications port = 18322
> Total events supported = 1
> Request Time Out = 250 milliseconds
> 
> The others:
> TSconfigure (0, 10, 60, 0, 0)
> -> TSreport
> Soft timing master
> Master timing IOC alive
> Time protocol sync with unix
> Clock Rate in Hertz = 60
> Sync Rate in Seconds = 10
> Master communications port = 18323
> Slave communications port = 18322
> Total events supported = 1
> Request Time Out = 250 milliseconds
> 
> 
> Any idea ???
> 
> Gabor Csuka
> DESY
> 

Navigate by Date:
Prev: Re: TS - EAST from GMT Marty Kraimer
Next: TS - EAST from GMT Gabor Csuka, DESY - Germany
Index: 1994  <19951996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: TS - EAST from GMT Andrew Johnson
Next: Re: IOC time 1min=90sec ?? winans
Index: 1994  <19951996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·