Subject: |
Re: Re: Asynchronous Momentary Binary Output Bug |
From: |
[email protected] |
Date: |
Fri, 15 Jul 94 12:31:20 -0500 |
>
>
>
> > 2a)The value 1 is written to the record and the record starts processing
> > Record processing calls device support which queues a request to the device
> > and tells record support that it has started asyn processing.
> > The 1st phase of processing completes. Record is unlocked but active.
>
> If PACT is TRUE via step 1, why does this record process when a value is
> written to it here?
PACT is no longer TRUE. Remember that honoring the HIGH field is done via a
completely new request for record processing. The PACT field is only kept
TRUE between asyn start and asyn completion.
Marty Kraimer