<19941995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index <19941995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: arAccessLib.c
From: [email protected]
Date: Thu, 07 Apr 94 07:46:46 -0500
> 
> 
> I'm using routines in arAccessLib.c to archive data on the IOC in a format
> which can be read by ARR.  I would like to archive unsigned shorts but
> there doesn't appear to be support for this.  Is this true?
> 
> Greg Greene
> KineticSystems Corp.
> (303) 220-7455 x13


Yes it is true. The archiver uses channel access which uses old database
access (defined in db_access.h). Old database access supports short
and long but not the unsigned varieties. If a DBR_LONG is requested for
a field type that is unsigned short then things will work but it does
of course take more storage.

Marty Kraimer

Navigate by Date:
Prev: Release 11 installation Gabor Csuka, DESY - Germany
Next: EPICS drivers for CAN Jeff Hill
Index: <19941995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: arAccessLib.c greene%denali . UUCP
Next: EPICS drivers for CAN Jeff Hill
Index: <19941995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 10 Aug 2010 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·