Experimental Physics and Industrial Control System
All,
It looks like the MLST (monitor last value) field of the boRecord is not
being initialized (always 0). The problem occurs if VAL is initialized
to 1 by device support (MLST still 0). Monitors are posted only if VAL
!= MLST. So setting VAL to 0 from 1 (MLST still 0) won't post a
monitor, and writing 1 will post an extra monitor.
I think the correct action is to set MLST=VAL at the end of the
init_record.
Does this seem appropriate?
Michael
- Replies:
- RE: missing monitors from boRecord (patch) Davidsaver, Michael
- Navigate by Date:
- Prev:
dbToRecordTypeH Benjamin Franksen
- Next:
RE: missing monitors from boRecord (patch) Davidsaver, Michael