Subject: Re: Ethernet/IP: writing zero to soft tags
From: Kay-Uwe Kasemir <[email protected]>
To: [email protected]
Date: Sat, 17 Dec 2005 13:38:58 -0500

On Dec 16, 2005, at 21:47 , John Dobbins wrote:

Dear All,

We have the following problem using Ethernet/IP device support (and EPICS R3.14.7) with an Allen-Bradley ControlLogix PLC. We can write to hardware output tags (things like Local:9:O.Data[1]) just fine, however when we try to write to a soft tag, i.e. a controller tag or a program tag, we find we can write a "one" but not a "zero".

What records do you have connected to the tag?
A single BO with
  SCAN="Passive"
  OUT="@plc Local:9:O.Data[1] S1"
?
Or multiple BOs for various bits in the same tag?
In the latter case, can you duplicate the problem
with a database that only contains a single BO?

Thanks,
-Kay


Navigate by Date:
Prev: Re: VDCT expand and template constructs Kay-Uwe Kasemir
Next: Re: VDCT expand and template constructs Andrew Johnson
Index: 2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: Re: VDCT expand and template constructs Kay-Uwe Kasemir
Index: 2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
ANJ, 02 Feb 2012 Valid HTML 4.01! · Home · News · About · Base · Modules · Extensions · Distributions · Download ·
· Search · EPICS V4 · IRMIS · Talk · Bugs · Documents · Links · Licensing ·