Equipment |
Hazards |
Engineered Controls |
Electrical Safety Training References |
Electrical Safety Procedures |
Mechanical Safety Training References |
Mechanical Safety Procedures |
Radiological, Environmental & Chemical Training References |
Radiological, Environmental & Chemical Procedures |
Additional Safety Tool References |
|
Acopian Power Supplies
Total 2
(Controls Group) |
24VDC
120VAC
Lifting |
120VAC covered
Doors closed
Signage
|
1 |
NA |
NA |
NA |
NA |
NA |
A ASD108/400 |
|
Best Uninterupptable Power Supply (UPS)
(Controls Group) |
24VDC
120VAC
Lifting |
120VAC covered
Doors closed
Signage
|
1 |
NA |
6, 7 |
NA |
NA |
NA |
A ASD108/400 |
|
Allen Bradley Programmable Logic Controllers (PLCs)
Total 4
(Controls Group) |
Lithium batteries
|
|
1 |
NA |
NA |
NA |
NA |
NA |
A, C
ASD108/400 |
|
Rack Mounted Equipment
(All Groups) |
24VDC
120VAC
Lifting |
120VAC covered
Doors closed
|
1 |
NA |
6, 7 |
NA |
NA |
NA |
A ASD108/400 |
|
LINAC Klystrons
Total 6
(RF Group)
(ME Group)
(Vac Group) |
High voltage
Ionizing radiation
Non-ionizing radiation
Lead
SF6 (waveguide)
High pressure water (150PSI) |
Electrical signage
Contacts covered
Ionizing radiation shielding
Vacuum interlocks (SF6, non-ionizing radiation)
Water shut-off valves
|
1 |
NA |
6, 7
ESH119 Pressure Safety Orientation
|
NA |
3, 4, 5 |
1110-00028 (Config. Control Policy for Supplemental Personnel Protection Radiation Shielding)
7-00511 (APS Proc. for Operational Response to Water Leaks)
|
A, B
ASD108/400 |
|
Magnet Power Supplies.
(3 per klystron)
(RF Group) |
208VAC 3-Phase
150VDC
40Amp DC |
Electrical signage
Contacts covered
Rack doors locked or bolted closed
|
1 |
1110-00113 (Start-up/ Shutdown, Incl. Emergency Shutdown, LOTO, and Call-In Proc. of the LINAC Magnets and Power Supplies)
|
NA |
NA |
NA |
NA |
A ASD108/400 |
|
Klystron Heater Supply
(RF Group) |
110VAC |
Electrical signage
Contacts covered
|
1 |
NA |
NA |
NA |
NA |
NA |
A ASD108/400 |
|
RF Modulators
Total 6
(RF Group) |
High current
High voltage
Stored energy |
Contacts covered
Kirk Key interlock
Ground stick
Signage/warning lights
Disconnect switches
|
1 |
7 |
NA |
NA |
NA |
NA |
A, B
ASD108/400 |
|
Thyratron Heater Supply
(RF Group) |
110VAC |
Electrical signage
Contacts covered
|
1 |
NA |
NA |
NA |
NA |
NA |
A ASD108/400 |
|
Modulator Control System
(RF Group) |
110VAC |
Electrical signage
Contacts covered
|
1 |
NA |
NA |
NA |
NA |
NA |
A ASD108/400 |
|
Sled Cavities
(RF Group) |
Ionizing radiation |
External shielding
|
NA |
NA |
NA |
NA |
2
ESH700 Rad. Worker I
|
NA |
A ASD108/400 |
|
DC Power Supplies
(PS Group) |
DC voltages < 300 Volts
DC currents < 500 Amps
AC voltages < 600 Volts
Lifting < 350 lbs |
Supplies mounted in relay racks
Rack doors locked or bolted closed
Power source signage
120/208/480 VAC covered
Lifting fixture
Emergency stop buttons
Flashing strobes
LOTO
|
1, 7 |
1110-00113
1110-00123
2502-00006
121-00021
121-00022
121-00023
121-00024
121-00025
31020101-00025
Power Supplies Hot Work Permits |
6 |
NA |
NA |
NA |
A ASD108/400 |
|
Pulsed Power Supplies
(PS Group) |
High voltages
High currents
Stored energy
Fans |
Supplies built in relay racks
Rack doors locked or bolted closed and interlocked
Power source signage
Hi voltage signage
120 VAC covered
Caps are shorted automatically
Shorting sticks
Fan blade covers
LOTO
|
1, 7 |
2502-00006
31020101-00025
Power Supplies Hot Work Permits |
6, 7 |
NA |
NA |
NA |
A, B
ASD108/400 |
|
GESPAC Power Supply Control Units
(PS Group) |
120 VAC
Fans |
Fan blades covered
Fan blade covered
|
1, 7 |
Power Supplies Hot Work Permit |
6, 7 |
NA |
NA |
NA |
A, B
ASD108/400 |
|
Linac Closed Loop Water Stations
(ME Group) |
480 VAC
120 VAC
Water temperature to 150F
Water pressure to 100-150psig
Noise
Lead
High voltage in power supplies
Possibility of standing water
High voltage on ion pumps |
Process control interlocks
Relief valves
Power supply cabinets locked up (authorized keyholders only)
LOTO
Noise barrier curtains
PPE (ear plugs)
|
1 |
NA |
6, 7
ESH 119 Pressure Safety Orientation |
7-00511 (APS Proc. for Operational Response to Water Leaks)
|
5 |
1110-00028 (Config. Control Policy for Supplemental Personnel Protection Radiation Shielding)
|
A ASD108/400 |
|
Secondary Process Water System
(ME Group) |
Water pressure to 100-150psig
Possibility of standing water
Noise
480 VAC
120 VAC |
Process control interlocks
LOTO
|
1 |
NA |
NA |
7-00511 (APS Proc. for Operational Response to Water Leaks) |
ESH174 Noise and Hearing Conservation
|
NA |
A ASD108/400 |
|
PC Gun Water System
(ME Group) |
480 VAC
120 VAC
Water temperature to 150F
Water pressure to 100-150psig
Noise
Lead
Possibility of standing water |
Process control interlocks
Relief valves
LOTO
PPE
|
1 |
NA |
6, 7 |
7-00511 (APS Proc. for Operational Response to Water Leaks)
|
5
ESH174 Noise and Hearing Conservation |
1110-00028 (Config. Control Policy for Supplemental Personnel Protection Radiation Shielding)
|
A ASD108/400 |
|
Johnson Controls
(ME Group) |
120 VAC |
LOTO
|
1 |
NA |
NA |
NA |
NA |
NA |
A ASD108/400 |
|
Modulator Power Supplies Water Flow System & Instrumentation
(ME Group) |
Water pressure to 100 psig
High voltage in power supplies
Possibility of standing water |
Power supply cabinets locked up (authorized keyholders only)
LOTO
|
NA |
NA |
6, 7 |
7-00511 (APS Proc. for Operational Response to Water Leaks) |
ESH174 Noise and Hearing Conservation
|
NA |
A ASD108/400 |
|
RF Klystron Water Flow System & Instrumentation
(ME Group) |
120 VAC
Water pressure to 100-150psig
Noise
Possibility of standing water
High voltage on ion pumps |
Power supply cabinets locked up (authorized keyholders only)
LOTO
|
1 |
NA |
6, 7 |
7-00511 (APS Proc. for Operational Response to Water Leaks) |
ESH174 Noise and Hearing Conservation
|
NA |
A ASD108/400 |
|
Laser Room/RF Test Area Water and Air Supplies
(ME Group) |
120 VAC
Water temperature to 150F
Water pressure to 100-150psig
Lead
High voltage in power supplies
Possibility of standing water
High voltage on ion pumps |
Access keys locked up (authorized keyholders only)
LOTO
|
1 |
NA |
6, 7 |
7-00511 (APS Proc. for Operational Response to Water Leaks)
|
5 |
1110-00028 (Config. Control Policy for Supplemental Personnel Protection Radiation Shielding)
|
A ASD108/400 |
|
Work Delegated to Water Group by RF Group
(ME Group) |
480 VAC
120 VAC
Water temperature to 150F
Water pressure to 100-150psig
Noise
Lead
X-rays from klystrons
High voltage in power supplies
Possibility of standing water
High voltage on ion pumps
SF6 |
Process control interlocks
Power supply cabinets locked up (authorized keyholders only)
LOTO
|
1 |
NA |
6, 7 |
NA |
4, 5
ESH700 Rad. Worker I |
1110-00028 (Config. Control Policy for Supplemental Personnel Protection Radiation Shielding)
|
A ASD108/400 |
|
Ion Pump Power Supplies (VAC Group) |
6000V |
Electrical Signage
Contacts Covered
Rack doors locked or bolted closed
|
1 |
1110-00072 (Ion Pump Emergency Shut-down and Re-start Proc. for Accelerator Vacuum Systems) |
6, 7 |
NA |
NA |
NA |
A ASD108/400 |
|
SF6 System |
400 psi gas pressure
24VDC
120VAC
SF6 |
Signage
Control cabinet locked
Safety committee review
|
1 |
6, 7 |
ESH119 Pressure Safety Orientation
|
4 |
NA |
NA |
A ASD108/400 |