RF Water Systems

Photos

RF Building - Process Water Distribution Piping
RF Building - Piping to Storage Ring RF Cavities
RF Klystron Piping
RF Loads Piping
RF Loads and Circulator - Piping and Instrumentation

Drawings

Piping and Instrument Diagram, Pump P-RF-1
Piping and Instrument Diagram, Pump P-RF-2
Piping and Instrument Diagram, Pump P-RF-3
Piping and Instrument Diagram, Pump P-RF-4
Piping and Instrument Diagram, Pump P-RF-5

System Components Data

6 systems dedicated to RF system components (Klystrons, circulators, loads, cavities, SCR, oil coolers)

        5 out of six systems serving RF 1 thru RF5

Nominal flow - 460 g.p.m.
Supply pressure - 120 psig
Available pressure - 90 psid
Supply temperature - 85F 0.5F
Pumps – centrifugal 3x4x10, 304 stainless steel, 3600 rpm 100 HP motor
There is one stand-by pump dedicated to RF1, RF2, and Booster pump, and another dedicated to RF3, RF4, and RF5 system pumps.
Piping main – 6 inch, schedule 10, 304 SS

        One RF water system is dedicated for equipment testing and miscellaneous loads

Nominal flow – 300 g.p.m.
Supply pressure – 150 psig
Available pressure – 110 psid
Supply temperature - 78F 0.5F
Pumps – centrifugal 2x3x10, 304 stainless steel, 3600 rpm 75 HP motor
System has a lead and stand-by pump.
Piping main – 4 inch, schedule 10, 304 SS

Water data for various RF components

Klystron

Nominal flow to collector – 400 g.p.m.
Nominal flow to body cavity – 6 g.p.m.
Nominal flow to output cavity – 10 g.p.m.
Supply temperature – 87-90F (not controlled directly, return from S.R. Cavities)
Supply pressure to collector – 40 psig
Supply pressure to body and output cavity – 120 psig
Interlocks – supply flow, return flow, return temperature

Circulator

Nominal flow – 18 g.p.m.
Supply pressure – 120 psig
Supply temperature - 85F 0.5F
Flow control – "Griswold" valve
Interlocks – supply flow, return flow, return temperature

200KW Load

Nominal flow – 24 g.p.m.
Supply pressure – 120 psig
Supply temperature - 85F 0.5F
Flow control – "Griswold" valve
Interlocks – return flow, return temperature

Storage Ring Cavities

Nominal flow – 300 g.p.m. (75 g.p.m. per call)
Supply pressure – 120 psig
Supply temperature - 85F 0.5F
Flow control – "Griswold" valve
Interlocks – return flow

RF Test Skid

Consists of four 300 KW loads (1.2 MW)

Nominal flow – 160 g.p.m. (40 g.p.m. per 300 KW load)
Supply pressure – 120 psig
Supply temperature - 85F 0.5F
Interlocks – return flow, return temperature