Pump Rounds - Secondary Systems

SECONDARY SYSTEMSVAC SKID
PUMP
NUMBER
JCI
NAME
A-B TEMP
(degf)
DP
(psi)
PWS-F
(gpm)
PWR-F
(gpm)
BYPASS
(% closed)
DISCH
(psi)
OILMAG
(ohms)
VFDFILT D.P.
(psi)
A-B TEMP
(degf)
MAG
(ohms)
FILT D.P.
DI H20
FILT D.P.
CH W
UV
Light
WATER
LEVEL
DATE/TIME
PW SEG 1P-SRVC-04A/B
P-501/502PSR04A-B78.0102353358100144OkOk27815.421Ok22016-02-09 08:49:54
PW SEG 2P-SRVC-06A/B
P-503/504PSR06A-B78.0105404400100138Ok10.0Ok37816.110Off02016-02-09 08:49:54
PW SEG 3P-SRVC-08A/B
P-505/506 PSR08A-B78.0111386384100160OkOk37816.920Ok22016-02-09 08:49:54
PW SEG 4P-SRVC-10A/B
P-507/508PSR10A-B78.0102364367100130OkOk37816.910Ok12016-02-09 08:49:54
PW SEG 5P-SRVC-12A/B
P-509/510PSR12A-B78.0104378380100140OkOk57817.210Ok12016-02-09 08:49:54
PW SEG 6P-SRVC-14A/B
P-511/512PSR14A-B78.0103340348100160OkOk27816.500Ok02016-02-09 08:49:54
PW SEG 7P-SRVC-16A/B
P-513/514PSR16A-B78.0107412413100160OkOk57816.810Ok12016-02-09 08:49:54
PW SEG 8P-SRVC-18A/B
P-515/516PSR18A-B78.0107383384100126OkOk27817.010Ok12016-02-09 08:49:54
PW SEG 9P-SRVC-20A/B
P-517/518PSR20A-B78.0106356352100140OkOk47816.712Ok12016-02-09 08:49:54
PW SEG 10P-SRVC-22A/B
P-519/520PSR22A-B78.0104347350100154OkOk27815.912Ok02016-02-09 08:49:54
PW SEG 11P-SRVC-24A/B
P-521/522PSR24A-B78.0104382385100146OkOk37815.810Ok02016-02-09 08:49:54
PW SEG 12P-SRVC-26A/B
P-523/524PSR26A-B78.0108330330100148OK9.7Ok37817.200Off12016-02-09 08:49:54
PW SEG 13P-SRVC-28A/B
P-525/526PSR28A-B78.0101327327100140OkOk37815.131Ok22016-02-09 08:49:54
PW SEG 14P-SRVC-30A/B
P-527/528PSR30A-B78.0116360353100156OkOk67816.420Ok02016-02-09 08:49:54
PW SEG 15P-SRVC-32A/B
P-529/530PSR32A-B78.0108368368100204OkOk37816.500Ok02016-02-09 08:49:54
PW SEG 16P-SRVC-34A/B
P-531/532PSR34A-B78.0115349350100198OkOk57817.910Ok12016-02-09 08:49:54
PW SEG 17P-SRVC-36A/B
P-533/534PSR36A-B78.099408402100142OkOk47816.120Ok02016-02-09 08:49:54
PW SEG 18P-SRVC-38A/B
P-535/536PSR38A-B78.0107284286100162OkOk67817.810Ok02016-02-09 08:49:54
RING WESTP-SRVC-40A/B
P-401/402PSR40A-B78.0109272279100150OkOk07810.520Ok12016-02-09 08:49:54
RING EASTP-SRVC-02A/B
P-404/405PSR02A-B78.0104353385100146OkOk47816.511Ok12016-02-09 08:49:54
PUMP
 NUMBER 
JCI
   NAME   
A-B TEMP
(degf)
DP
(psi)
PWS-F
(gpm)
PWR-F
(gpm)
BYPASS
(% closed)
DISCH
  (psi)  
OILMAG
(ohms)
VFDFILT D.P.
(psi)
DATE/TIME
EAA
P-403PSREAA78.095110110100138OkOk32016-02-09 08:49:54
SPX
P-SPX 78.0708583100OkOk82016-02-09 08:49:54
NAMECOMMENTSDATE/TIME
John Dench2016-02-09 08:49:54

Pump Rounds - RF/LINAC/INJECTION

PUMP
NUMBER
SERVICEA-B TEMP
(degf)
SET POINT TEMP
(degf)
PWS-F
(gpm)
PWR-F
(gpm)
D.P.BYPASS
(% closed)
DISCH
(psi)
OILMAG
(ohms)
VFDFILT D.P.
(psi)
DATE/TIME
BLDG. 411/412
P-101TUNNEL90.09095.093.490.0100122Ok Ok02016-02-10 08:36:36
P-102GALLERY90.09028428857.90.0122Ok Ok 12016-02-10 08:36:36
P-103STANDBY0.002016-02-10 08:36:36
P-201PAR (INJ)80.08040340584.3100121Ok Ok42016-02-10 08:36:36
P-301ST. SOUTH90.090292287117100122Ok Ok 02016-02-10 08:36:36
P-302STANDBY0.002016-02-10 08:36:36
LEUTLLEUTL0.002016-02-10 08:36:36
P-PR-MOD1MODULATORS0.002016-02-10 08:36:36
P-PR-MOD2MODULATORS0.0426712016-02-10 08:36:36

DISSOLVED
OXYGEN
MAG
(ohms)
DATE/TIME
D.O.3.02016-02-10 08:36:36
RESISTIVITY10.12016-02-10 08:36:36

PUMP
NUMBER
SERVICEA-B TEMP
(degf)
SET POINT TEMP
(degf)
PWS-F
(gpm)
PWR-F
(gpm)
D.P.BYPASS
(% closed)
DISCH
(psi)
OILMAG
(ohms)
VFDFILT D.P.
(psi)
DATE/TIME
BLDG. 420
P-901RF-186.08653953298.1100129Ok 10.3Ok 52016-02-10 08:36:36
P-902RF-285.08550950497.7100128Ok Ok 52016-02-10 08:36:36
P-303ST. NORTH90.090402465113100147Ok Ok 42016-02-10 08:36:36
P-903STANDBY0.002016-02-10 08:36:36
P-910RF-TS180.08051952230.073.7190Ok 42016-02-10 08:36:36
P-904STANDBY0.002016-02-10 08:36:36
P-905RF-585.08553953894.0100122Ok Ok 42016-02-10 08:36:36
P-906RF-385.08552751789.7100131Ok Ok 62016-02-10 08:36:36
P-907RF-489.08948648793.2100140Ok 10.6Ok 52016-02-10 08:36:36
P-908RF LOADS85.085407397106100117Ok 32016-02-10 08:36:36
P-909STANDBY 0.002016-02-10 08:36:36

NAMECOMMENTSDATE/TIME
Bob Furst2016-02-10 08:36:36